1 hazardous location considerations – Spectrum Controls 1762sc-IF4OF4 User Manual

Page 14

Advertising
background image

2-2

MicroLogix™ 1200 Analog Combo Module (4Ch IN / 4Ch Out)



User’s Manual Pub. 0300247-01 Rev. C

5 VDC 24 VDC

30 mA 3.0W Max (125mA max at 24V)


Use the table below to determine the maximum number of IF4OF4 modules that can be
installed in a MicroLogix system.

Table 2-1

Controller

Max 5V

Bus Current

Max 24V

Bus Current Max # of IF4OF4 Modules

ML1100 800

700

4

ML1200 (24pt.)

400

350

3

ML1200 (40pt.)

600

500

3

ML1400 (All)

1500

1500

7

Section 2.3
General
Considerations

1762 I/O is suitable for use in an industrial environment when installed in accordance
with these instructions. Specifically, this equipment is intended for use in clean, dry
environments Pollution degree 2

1

and to circuits not exceeding Over Voltage Category

II

2

(IEC 60664-1)

3

.

2.3.1 Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-
hazardous locations only. The following WARNING statement applies to use in
hazardous locations.




1

Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that

occasionally a temporary conductivity caused by condensation shall be expected.

2

Over Voltage Category II is the load level section of the electrical distribution system. At this level

transient voltages are controlled and do not exceed the impulse voltage capability of the product’s
insulation.

3

Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)

designations.

Advertising