A-2

MicroLogix™ 1200 Analog Combo Module (4Ch IN / 4Ch Out)

User’s Manual Pub. 0300247-01 Rev. C

Specification

Value

Hazardous
Environment
Class

Class I, Division 2, Hazardous Location, Groups A, B,
C, D
(ISA 12.12.01, C-UL under CSA C22.2 No. 213)
Operating Temperature Code T4a

Radiated and
Conducted Emissions

EN55011

Electrical /EMC:

The module has passed testing at the following levels:

ESD Immunity
(IEC61000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity
(IEC61000-4-3)

10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed
carrier

Fast Transient Burst
(IEC61000-4-4)

2 kV, 5 kHz

Surge Immunity
(IEC61000-4-5)

1 kV galvanic gun

Conducted Immunity
(IEC61000-4-6)

10V, 0.15 to 80 MHz

6

Input Specifications

Specification

Value

Number of Inputs

2 Current only and
2 Current/Voltage/Thermocouple

A/D Converter Type

Delta Sigma

Common Mode Rejection

75 dB for 4 Hz & 17 Hz Filters

Normal Mode Rejection

4 Hz Filter

74dB minimum at
50 and 60 Hz

17 Hz Filter

65dB minimum at
50 and 60 Hz

62 Hz Filter

First notch at
31Hz, typically
30dB

470 Hz Filter

First notch at 237
Hz, typically 35dB

Non-linearity (in percent full
scale)

±0.1%

Input Impedance

Current Terminal: 249Ω

Current Input Protection

±42 mA

Voltage Input Protection

±28 V

7




6

Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 2700

MHz.

7

The input voltage on any input pin must be within ±13VDC of the output return lines for normal operation.