Spectrum Controls 1762sc-IF4OF4 User Manual

Page 8

Advertising
background image

1-2

MicroLogix™ 1200 Analog Combo Module (4Ch IN / 4Ch Out)



User’s Manual Pub. 0300247-01 Rev. C

Section 1.3
Input Types
and Ranges

The table below lists the input types and their associated ranges.

Table 1-2 (Input Types)
Input Type

Range

E Type Thermocouple

-200 to 1000 ˚C

(-328 to 1832 ˚F)

J Type Thermocouple

-180 to 1200 ˚C

(-292 to 2192 ˚F)

K Type Thermocouple

-200 to 1370 ˚C

(-328 to 2498 ˚F)

T Type Thermocouple -190 to 400 ˚C

(-310 to 752 ˚F)

Voltage

0 to 5V (0 to 5.5V)
1 to 5V (0 to 5.5V)
+/- 10V (-11 to +11V)
0 to 10V (0 to 11V)

Current

4 to 20 mA (3.92 to 20.4 mA)
0 to 20 mA (0 to 20.4 mA)

!

Attention

Channels 4 and 5 can be configured for current inputs only, and
support current input ranges as shown in Table 1-2

!

Attention

Channels 6 and 7 can be configured for either current or voltage
inputs. Current support includes input ranges as shown in Table
1-2. Voltage input ranges include both thermocouple and Voltages as
defined in Table 1-2

Section 1.4
Data Formats

For input channels, the data can be configured for:

 Engineering units x1
 Engineering units x10
 Scaled-for-PID
 Raw/proportional data

For output channels, the data can be configured for:

 Engineering units
 Scaled for PID
 Raw/proportional data
 Percent range