Spectrum Controls 1794sc-IF8IU User Manual

Page 18

Advertising
background image

2-8

Flex™ IO Isolated Universal Input Module



User's Manual Pub. 0300231‐01 Rev. A

To install the mounting plate on a wall or panel:

1) Lay out the required points on the wall/panel as shown in the drilling dimension

drawing.

Drilling Dimensions for Panel/Wall Mounting of Flex IO

2) Drill the necessary holes for the #6 self-tapping mounting screws.
3) Mount the mounting plate (1) for the adapter module using two#6 self-tapping

screws (18 included for mounting up to 8 modules and the adapter).

!

Attention

Make certain that the mounting plate is properly grounded to the
panel. Refer to “Industrial Automation Wiring and Grounding
Guidelines,” publication1770-4.1.

4) Hold the adapter (2) at a slight angle and engage the top of the mounting plate in

the indention on the rear of the adapter module.

5) Press the adapter down flush with the panel until the locking lever locks.
6) Position the terminal base unit up against the adapter and push the female bus

connector into the adapter.

7) Secure to the wall with two #6 self-tapping screws.
8) Repeat for each remaining terminal base unit.