Spectrum Controls 1794sc-IF8IU User Manual

Page 48

Advertising
background image

A-2

Flex™ IO Isolated Universal Input Module



User's Manual Pub. 0300231‐01 Rev. A

Data format

Engineering Units X1
Engineering Units X10
Raw/Proportional Counts
Scaled for PID
Percent of full scale

Input Impedance

>1 M ohms for voltage, thermocouple, RTD
and resistance inputs
249Ω +/- 1% for current inputs

Common mode rejection

60 db @ 5V peak-to-peak, 50…60 Hz

Isolation voltage (continuous voltage
withstand rating)

User power to Backplane:24 VDC continuous
Channel to Backplane: 24 VDC continuous
Channel to Channel: 24 VDC continuous.
Channel to User power: 24 VDC continuous

Open circuit protection

Open circuit detection bias <1 uA with
ON/OFF capability

Overvoltage capability

Voltage mode ± 24 VDC continuous (ten
minutes)
Current mode ± 7.8 VDC continuous (ten
minutes)

Cold junction compensation Range

-20…100 °C

Cold junction compensator

A-B catalog number 1794-CJC2

Flexbus current

80 mA

Power dissipation

7.25 W max @ 31.2V dc

Thermal dissipation

Max 10.2 BTU/hr @ 31.2V dc

Keyswitch position

3


Module Accuracy

Thermocouple Accuracy
with 4.17 Hz filter
using Linearization per ITS-90

Accuracy
Limit At
25°C
4.17 Hz
Filter

Accuracy
Limit At 0-
55°C
4.17 Hz
Filter

Repeatability
Limit
At 25°C & 4.17
Hz filter

Type J (-50˚C to 1200˚C):

± 0.6 °C

± 2.3 °C

± 0.17 °C

Type J (-210˚C to -50˚C):

± 0.8 °C

± 3.3 °C

± 0.25 °C

Type N (-80˚C to 1300˚C):

± 1.0 °C

± 1.5 °C

± 0.3 °C

Type N (-250˚C to -80˚C):

± 1.2 °C

± 3.0 °C

± 1.9 °C

Type T (-180˚C to 400˚C):

± 1.0 °C

± 1.5 °C

± 0.2 °C

Type T (-270˚C to -180˚C):

± 5.4 °C

± 8.5 °C

± 1.5 °C

Type K (-180˚C to 1370˚C):

± 1.0 °C

± 1.5°C

± 0.3 °C

Type K (-270˚C to -180˚C):

± 7.5 °C

± 11.5 °C

± 3.6 °C

Type E (-130˚C to 1000˚C):

± 0.5 °C

± 1.5 °C

± 0.1°C

Type E (-270˚C to -130˚C):

± 4.2 °C

± 7.3 °C

± 1.2 °C

Type C (0˚C to 2315˚C):

± 1.8 °C

± 3.5 °C

± 0.9 °C

Type B (600˚C to 1800˚C):

± 3.0 °C

± 4.0 °C

± 1°C

Type B (300˚C to 600˚C):

± 3.0 °C

± 8.0 °C

± 2°C

Type S (140˚C to -1760˚C):

± 1.7 °C

± 2.6 °C

± 0.55 °C

Type S (0˚C to 140˚C):

± 1.7 °C

± 5.0 °C

± 1.0 °C

Type R (280˚C to -1760˚C):

± 1.7 °C

± 2.6 °C

± 0.4 °C

Type R (0˚C to 280˚C):

± 1.7 °C

± 5.0 °C

± 1.0 °C

CJC accuracy

± 1.0 °C

3.0 °C

± 0.8 °C

Advertising