Spectrum Controls 1794sc-IF8IU User Manual

Page 20

Advertising
background image

2-10

Flex™ IO Isolated Universal Input Module



User's Manual Pub. 0300231‐01 Rev. A

is seated when the latching mechanism (7) is locked into the module.

6) Repeat the above steps to install the next module in its terminal base unit.

Section 2.5
Field Wiring
Connections

Wiring to the IF8IU module is made through the terminal base unit on which the module
mounts. Compatible terminal base units are:

Module 1794-TB3G

1794-TB3GS

1794sc-IF8IU Yes

Yes

2.5.1 Field Wiring using a 1794-TB3G and TB3GS Terminal Base

1) Connect the individual signal wiring to numbered terminals on the 0–15 row (A)

and 17–32 row(B) on the terminal base unit. Connect the input devices as
shown in the wiring table on page 2-11 .

2) Terminate shields: to terminals 16 or 33 on row B, or 40 through 45 on row C.
3) Connect +24V dc to terminal 34 on the 34-51 row (C), and 24V common to

terminal 35 on the 34-51 row (C).

!

Attention

To reduce susceptibility to noise, power IF8IU modules and digital
modules from separate power supplies. Do not exceed a length of 33ft
(10m) for dc power cabling.

4) If daisy chaining the +24V dc power to the next base unit, connect a jumper

from terminal 50 (+24V) on this base unit to terminal 34 and from terminal 51
(24V dc common) to terminal 35 on the next base unit.

!

Attention

Do not daisy chain power or ground from the IF8IU terminal base unit
to any ac or dc digital module terminal base unit.