Spectrum Controls 1794sc-IF8IU User Manual

Page 38

Advertising
background image

3-12

Flex™ IO Isolated Universal Input Module



User's Manual Pub. 0300231‐01 Rev. A

Input Type

Range

Eng. Units

Eng Units X10 Raw/Prop

PID

Percent

10 Ω Cu α 0.426

-100 to 260 ˚C
(-148 to 500 ˚F)

-1000 to 2600
(-1480 to 5000)

-100 to 260
(-148 to 500)

-32768 to 32767

0 to 16383

0 to 10000

100 Ω Ni α 0.618

-100 to 260 ˚C
(-148 to 500 ˚F)

-1000 to 2600
(-1480 to 5000)

-100 to 260
(-148 to 500)

-32768 to 32767

0 to 16383

0 to 10000

120 Ω Ni α 0.672

-80 to 260 ˚C
(-112 to 500 ˚F)

-800 to 2600
(-1120 to 5000)

-80 to 260
(-112 to 500)

-32768 to 32767

0 to 16383

0 to 10000

604 Ω NiFe α 0.518

-100 to 200 ˚C
(-148 to 392 ˚F)

-1000 to 2000
(-1480 to 3920)

-100 to 200
(-148 to 392)

-32768 to 32767

0 to 16383

0 to 10000

Resistance

0 to 150 Ω

0 to 15000

0 to 1500

-32768 to 32767

0 to 16383

0 to 10000

0 to 1000 Ω

0 to 10000

0 to 1000

-32768 to 32767

0 to 16383

0 to 10000

0 to 3000 Ω

0 to 30000

0 to 3000

-32768 to 32767

0 to 16383

0 to 10000

Voltage

+/- 50 mV

-5000 to 5000

-500 to 500

-32768 to 32767

0 to 16383

0 to 10000

+/- 100 mV

-10000 to 10000

-1000 to 1000

-32768 to 32767

0 to 16383

0 to 10000

0 to 5V

0 to 5000

0 to 500

-32768 to 32767

0 to 16383

0 to 10000

1 to 5V

1000 to 5000

100 to 500

-32768 to 32767

0 to 16383

0 to 10000

+/- 10V

-10000 to 10000

-1000 to 1000

-32768 to 32767

0 to 16383

0 to 10000

0 to 10V

0 to 10000

0 to 1000

-32768 to 32767

0 to 16383

0 to 10000

Current

4 to 20 mA

4000 to 20000

400 to 2000

-32768 to 32767

0 to 16383

0 to 10000

0 to 20 mA

0 to 20000

0 to 2000

-32768 to 32767

0 to 16383

0 to 10000

3.4.5 Open Circuit Mode [Words 1 – 8 (Bits 12 & 13)]

The open circuit mode determines the fail-safe data value each channel is to default to in
the event of an open circuit condition. The table below lists the available options.

Table 3-7 (Open Circuit Mode)
Bit 13 Bit 12 Open Circuit Mode:
0

0

Zero analog value on broken input.

0

1

Set analog value to Max scale on broken input.

1

0

Set analog value to Min scale on broken input.

1 1 Previous

Value

3.4.6 Disable CJC [Words 1 – 8 (Bit 14)]

This bit is used to disable CJC compensation for the associated channel.

Table 3-8 (Disable CJC)
State Function
0 CJCs

Enabled

1

1 CJCs

Disabled

1

1

This field is only used if the input type is a thermocouple and the

format is not a CJC format. No compensation is performed on the
thermocouple when disabled.

3.4.7 Temperature Units [Words 1 – 8 (Bit 15)]

This bit enables Celsius or Fahrenheit for the associated channel.

Note: If the associated channel is not configured for an RTD or
thermocouple, the temperature units have no effect.


Table 3-9 (Temperature Units)
State Function
0 Degrees

C

1 Degrees

F