Table 3-2 (Fault Mode)
State Function
0 Disabled
1

Enable Broken Wire Detection

3.4.2 Input Type [Words 1 – 8 (Bits 0 to 4)]

Use the table below to select the input type for each channel.

Table 3-3 (Input Type)
Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Range:
0 0 0 0 0 B

Type

Thermocouple

0 0 0 0 1 C

Type

Thermocouple

0 0 0 1 0 E

Type

Thermocouple

0 0 0 1 1 J

Type

Thermocouple

0 0 1 0 0 K

Type

Thermocouple

0 0 1 0 1 N

Type

Thermocouple

0 0 1 1 0 R

Type

Thermocouple

0 0 1 1 1 S

Type

Thermocouple

0 1 0 0 0 T

Type

Thermocouple

0 1 0 0 1 100

Ω Pt α 0.385

0 1 0 1 0 200

Ω Pt α 0.385

0 1 0 1 1 500

Ω Pt α 0.385

0 1 1 0 0 1000

Ω Pt α 0.385

0 1 1 0 1 100

Ω Pt α 0.3916

0 1 1 1 0 200

Ω Pt α 0.3916

0 1 1 1 1 500

Ω Pt α 0.3916

1 0 0 0 0 1000

Ω Pt α 0.3916

1 0 0 0 1 10

Ω Cu α 0.426

1 0 0 1 0 100

Ω Ni α 0.618

1 0 0 1 1 120

Ω Ni α 0.672

1 0 1 0 0 604

Ω NiFe α 0.518

1 0 1 0 1 R

0

to

150

1 0 1 1 0 R

0

to

1000

1 0 1 1 1 R

0

to

3000

1 1 0 0 0 +/-

50

mV

1 1 0 0 1 +/-

100

mV

1 1 0 1 0 0

to

5V

1 1 0 1 1 1

to

5V

1 1 1 0 0 +/-

10V

1 1 1 0 1 0

to

10V

1 1 1 1 0 4

to

20

mA

1 1 1 1 1 0

to

20

mA

3.4.3 Input Filter [Words 1 – 8 (Bits 5 to 7)

Use the table below to select the appropriate filter for each channel.

Table 3-4 (Filter Settings)
Bit 7 Bit 6 Bit 5 ADC Filter:
0 0 0 4.17

Hz

0 0 1 10.0

Hz