TROUBLESHOOTING

Symptom

Possible Cause

What To Do

UPS will not turn on

On/Off button not pressed

Press and release the On/Off button
to start UPS

UPS operates in battery mode only,
even though there is normal AC
present

Input AC circuit breaker is tripped

Reset circuit breaker by pressing
the plunger back in. If the AC
circuit breaker trips after UPS starts
up, reduce the load on the UPS

Fault LED is illuminated

UPS has detected an internal fault

Call for service

The AC Mode LED is illuminated,
but there is no output

The UPS is being controlled via its
communications port

Disconnect the computer cable
from the UPS and press the On
button. If UPS works normally, the
software has control of the UPS

UPS does not provide expected
runtime

The batteries may be weak or at the
end of useful service life

Charge the batteries for 8 hours and
retest. If the runtime is still less
than expected, the batteries may
need to be replaced, even though
the Weak/Bad Battery LED is not
illuminated.

Bad Battery LED is illuminated

Loose connections at the batteries,
Weak batteries, Bad batteries

Check battery connections, charge
the batteries for 8 hours, replace the
batteries.

Overload LED is illuminated

The load has exceeded the UPS’s
capacity

Check the specifications (See
Specifications section). Remove
part of the load

The AC Mode LED is blinking
once every second and the audible
alarm is silent

The UPS is operating in the Boost
Mode

The UPS is performing its intended
function

The AC Mode LED is blinking
twice every second and the audible
alarm is silent

The UPS is operating in the Buck
Mode

The UPS is performing its intended
function