Surge Protection Specifications

Surge Protection: Advanced Series Mode® surge elimination

Surge Energy Rating: 6,000 volts/3,000 amps

Let through Voltage (6,000 volt surge): 0 volts

UL 1449 Adjunct Classification Test Results: 1000 surges, 6000 volts, 3000 amps, B3 pulse; Measured
suppressed voltage: 170 volts; no failures.

Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)

EMI/RFI Filter, Normal Mode (50-ohm load): 40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50
dB @ 30 MHz
EMI/RFI Filter, Common Mode (50-ohm load): 18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50
dB @ 20 MHz

Maximum Applied Surge Voltage: 6000 volts*
Maximum Applied Surge Current: Unlimited, due to current limiting*
Maximum Applied Surge Energy: Unlimited, due to current limiting*
Endurance (C62.41-1991 Category B3 pulses): 1kV>500,000; 3 kV>10,000; 6 kV>1000

General Specifications

Product Warranty: (USA and Canada only) 3-year limited warranty
Battery Warranty:

3-year limited warranty

Monitoring Software: Includes SentryPlus software
Communications: USB
Rack Size: 2U
Unit Dimensions (H x W x D): 3.5” x 19.0” x 10.5”
Unit Weight (lbs.): 32.0 lbs.
Operating Temperature: 32°F to 104°F (up to 5,000 ft above sea level (0°C to +40°C (up to 1,500 meters
above sea level)
Operating Elevation: 32°F to 95°F (5,001-10,000 ft above sea level (0°C to +35°C (1,501 to 3,000 meters
above sea level)
Storage Temperature/Relative Humidity: 5°F to 113°F (-15°C to +45°C) / 0 - 95% non-condensing
Humidity Range: 5% to 95% R.H., non-condensing

* 1.2 x 50 μs pulse, industry standard combination wave surge, as per IEEE C62.41.