SurgeX SU-1000Li User Manual

Page 8

Advertising
background image

SU1000Li Manual

7

SPECIFICATIONS

AC Input
Number of Phases:
Single (2W + G)
Power Cord: 6-ft. grounded, 3 wire, #14 line cord
Input Voltage (Acceptable Input Voltage): 120VAC (0 - 160VAC)
Input Voltage Range (Normal mode): 90 - 150VAC
DC Start Capability: Yes, (defaults to 60Hz)
Power Requirements (no load): 35 watts (charging), 15 watts (charged)



AC Output (Normal Mode)
Load Rating:
15 Amps @ 120 volts
Load Power Factor: 0.6
Outlets: 6 outlets (15 Amp) all with Advanced Series Mode surge elimination, 2 outlets with battery back-up
Output Frequency: Same as Input
Short Circuit Protection: Re-settable circuit breaker and electronically limited
Overload Capability: 110% - 5 minutes

≥120% - immediate shutdown

Output Voltage Regulation: 120VAC: -12.5% to +8.4%
Waveform: Same as Input
Boost Mode Voltage (Buck mode voltage): Nominal +16% (Nominal -14%)
Line Mode Voltage Range: 105 - 130VAC
Efficiency:
Normal mode > 90%



AC Output (Battery Mode)
Capacity:
1000VA/600W
Back-up Run Time:
4 minutes 600W full load, 10.4 minutes 300W half load
Output voltage: Nominal 120VAC
Waveform:
Stepped sine wave (simulated sine wave)
Topology: Single boost/buck line interactive, simulated sine wave
Battery Mode Voltage Regulation: Nominal ± 6% until LBW
Transfer Time: 6-10 ms
Output Frequency & Regulation:
50/60Hz ± 0.5Hz (Unless synchronized to utility)
Short Circuit Protection: Active electronic (current limit)



Batteries
Battery Rating:
(2) 12V/7AH
Replacement: Hot swappable
Recharge Time:
8 hours to 90% after full load discharge


Advertising