SurgeX SU-1000Li User Manual

Page 7

Advertising
background image

SU1000Li Manual

6

REPLACING THE BATTERY (Qualified Service Personnel Only)

Please read all warnings and cautions before attempting to service the batteries.

WARNING! This UPS contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond
the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and battery
replacement must be performed by Qualified Service Personnel Only.
CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be
toxic.
CAUTION: Do not dispose of batteries in a fire. The batteries may explode. The batteries in this UPS are
recyclable. Dispose of the batteries properly. The batteries contain lead and pose a hazard to the environment
and human health if not disposed of properly. Refer to local codes for proper disposal requirements or return the
battery to the supplier.
CAUTION: Although the battery system voltage is only 12VDC and 24VDC the battery system can still
present a risk of electric shock. These batteries produce sufficient current to burn wire or tools very rapidly,
producing molten metal. Observe these precautions when replacing the batteries:

1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear, rubber gloves, and boots.
4. Do not lay tools or other metal parts on top of the batteries.
5. Disconnect the charging source prior to connecting or disconnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the battery is, remove the source of the

grounding. Contact with any part of a grounded battery can result in an electrical shock. The
likelihood of such shock will be reduced, if such grounds are removed during installation and
maintenance.

Battery Replacement Procedure

PLEASE READ THE CAUTIONS AND WARNING BEFORE ATTEMPTING TO REPLACE THE
BATTERIES

BATTERY INFO:

Battery Qty/Rating: 2 units-12V7Ah
First Power Part #: FP1270
CSB Part #: GP1272

1.

Turn off the equipment that is plugged into the output receptacles of the UPS.

2.

Press and release the On/Off Button to turn the UPS off.

3.

Unplug the UPS’s power cord from the AC wall outlet.

4.

Unplug the equipment from the output receptacles of the UPS.

5.

Unplug the computer interface cable from the UPS

6.

Remove the screws from the Battery Access panel and carefully slide batteries out.

7.

Disconnect all connections (red and black) noting attachment points and wire colors/connections

8.

Do not short the battery wires together – Remove batteries and set aside.

9.

Orient new batteries in the same direction as original batteries.

10.

Connect black wires first, followed by red wire connections – Some sparking may occur, this is normal.

11.

Carefully slide the batteries back into the UPS.

12.

Re-install battery compartment cover and retaining screws.