Electrical connections, General, 208 volt operation – WaterFurnace Envisio Series Console User Manual

Page 18: Microprocessor remote thermostat wiring

Advertising
background image

18

ENVISION CONSOLE INSTALLATION MANUAL

Electrical Connections

General

Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wir-

ing must be done in accordance with local codes or the National Electric Code, whichever is applicable.

208 Volt Operation

All Envision Series 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue trans-

former wires must be switched.

Microprocessor Remote Thermostat Wiring

TB

O

G

Y

C

R

L

S

X2

X1

W2

Field

Connections

Unit

Connections

24 VAC

COMMON

COMPRESSOR

REVERSING

VALVE

FAN

LOCKOUT

SIGNAL

SHUTDOWN

NIGHT

SETBACK

LOAD SHED

Requires common

connections or 24

VAC for activation

Red

Black

Yellow

Orange

Green

Brown

Blue

Violet

Pink

Figure 5

Advertising