41

ENVISION CONSOLE INSTALLATION MANUAL

Pressure Drop

Model

GPM

Pressure Drop (psi)

30°F

50°F

70°F

90°F

110°F

1.2

1.0

0.9

0.8

0.7

0.6

09

1.8

2.3

2.2

2.0

1.9

1.8

2.5

3.8

3.7

3.5

3.3

3.1

1.5

0.9

0.8

0.7

0.6

0.5

12

2.3

1.7

1.5

1.4

1.3

1.1

3.5

3.0

2.7

2.5

2.4

2.2

2.0

1.7

1.6

1.5

1.4

1.3

15

3.0

3.3

3.2

3.0

2.9

2.8

4.5

5.7

5.5

5.3

5.1

4.9

3.0

1.7

1.6

1.5

1.4

1.3

18

4.0

4.1

4.0

3.9

3.7

3.6

5.5

7.9

7.6

7.4

7.2

6.9