Envision console controls cont, Inputs and outputs configuration, Control accessories – WaterFurnace Envisio Series Console User Manual

Page 34: Field selectable options

Advertising
background image

34

ENVISION CONSOLE INSTALLATION MANUAL

Inputs and Outputs Configuration

Field Selectable Options

Freeze Detection Limit Set Point (BI-5)

The freeze detection limit set point input allows you to

adjust the freeze detection limit set point (AI-5). When the

jumper is installed on BI-5 (Wire #24) the freeze detection

limit set point is factory set for 30°F. When the jumper on

BI-5 (Wire #24) is removed the freeze detection limit set

point will be 15°F.

Accessory Outputs (BO-7 and BO-8)

Accessory Output 1 will be energized 90 seconds prior

to the compressor output being energized. Accessory

Output 2 will be energized with the fan output (BO-1).

When the corresponding compressor output is turned

off the accessory output will be deactivated immediately.

These outputs are selectable for normally open or normally

closed operation through the Medium User interface or

through the Building Automation System.

Control Accessories

Zone Sensors

• TAXXJ02 Room Command Module

• TAXXA01 LCD Room Command Module

• A99

Sensor

MUI (LCD User interface) for diagnostics

and commissioning.

• MUIK3 - Panel Mount, Portable

• MUIK4 - Wall Mount

Envision Console Controls cont.

Input Name

Input

Output Name

Output

Zone Temp 1

AI 1

Fan Enable

BO1

Relative Humidity Input

AI 2

Comp – Low Capacity

BO2

Condensate Level

AI 3

Reversing Valve

BO3

Universal Temp Input

AI 4

Comp – Full Capacity

BO4

Water Coil Low Temperature Limit

AI 5

Network Output/EH Output

BO5

Warm/Cool Adjust and Temp Occ

AI 6

Alarm

BO6

Accessory 1 Output

BO7

Occupied

BI 1

Accessory 2 Output

BO8

Emergency Shutdown

BI 2

Network Controlled Output

B09

Stage 1 Low Pressure

BI 3

Network Viewable Input 1

BI 4

ECM2 Fan

PWM1

Water Coil Low Temp Limit Set Point

BI 5

Network Controlled Output

PWM2

Network Viewable Input 2

BI 6

Thermostat Y1

BI 7

Thermostat Y2

BI 8

Thermostat O

BI 9

Thermostat G

B10

Stage 1 High Pressure

BI11

Compressor Proving

BI12

XP10 Expansion Card

Input Name

Input

Output Name

Output

Unused

AI 1

Unused

BO 1

Unused

AI 2

Unused

BO 2

Unused

AI 3

Unused

BO 3

Unused

AI 4

Unused

BO 4

SINGLE and DUAL STAGE WATER-TO-AIR