Unit operating parameters, Unit operating limits, Unit operating limits unit operating parameters – WaterFurnace Envisio Series Console User Manual

Page 39: Single speed models

Advertising
background image

39

ENVISION CONSOLE INSTALLATION MANUAL

Entering

Water Temp

°F

Water Flow

GPM/Ton

Cooling

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

09-18

Superheat

09-18

Subcooling

Water Temp

Rise °F

Air Temp

Drop °F DB

50

1.5

127 - 144

205 - 225

5 - 10

10 - 14

18 - 22

18 - 22

3.0

120 - 140

185 - 205

7 - 15

5 - 10

8 - 10

18 - 22

70

1.5

139 - 154

280 - 300

8 - 11

8 -12

18 - 22

18 - 22

3.0

137 - 152

250 - 270

9 - 12

7 - 11

8 - 10

18 - 22

90

1.5

143 - 158

360 - 380

8 - 11

9 - 13

18 - 22

16 - 20

3.0

141 - 156

330 - 350

9 - 12

8 - 12

8 - 10

16 - 20

Entering

Water Temp

°F

Water Flow

GPM/Ton

Heating

Suction

Pressure

PSIG

Discharge

Pressure

PSIG

09-18

Superheat

09-18

Subcooling

Water

Temp Drop

°F

Air Temp

Rise °F DB

30

1.5

73 - 79

279 - 304

7 - 13

2 - 6

7 -10

18 - 24

3.0

79 - 85

285 - 310

8 - 14

2 - 6

3 - 6

20 - 26

50

1.5

103 - 109

308 - 333

8 - 12

4 - 8

8 - 11

20 - 26

3.0

110 - 116

315 - 340

9 - 13

4 - 8

4 - 7

22 - 28

70

1.5

140 - 146

330 - 365

10 - 14

7 - 11

11 - 14

26 - 32

3.0

146 - 153

340 - 375

10 - 14

7 - 11

7 - 10

28 - 34

Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.

Operating Limits

(°F)

(°C)

(°F)

(°C)

Air Limits

Min. Ambient Air

45

7.2

45

7.2

Rated Ambient Air

80

26.7

70

21.1

Max. Ambient Air

100

37.8

85

29.4

Min. Entering Air

50

10.0

40

4.4

Rated Entering Air db/wb

80.6/66.2

27/19

68

20.0

Max. Entering Air db/wb

110/83

43/28.3

80

26.7

Water Limits

Min. Entering Water

30

-1.1

20

-6.7

Normal Entering Water

50-110

10-43.3

30-70

-1.1

Max. Entering Water

120

48.9

90

32.2

Notes:

Cooling

Heating

Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy

temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The

operating limits are dependant upon three primary factors: 1) water temperature, 2) return air temperature, and 3)

ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be

at the normal level for proper and reliable unit operation.

Unit Operating Limits

Unit Operating Parameters

Single Speed Models