Auxiliary heat ratings, Blower performance data, Auxiliary heat ratings blower performance data – WaterFurnace Envisio Series Console User Manual

Page 20

Advertising
background image

20

ENVISION CONSOLE INSTALLATION MANUAL

Auxiliary Heat Ratings

Blower Performance Data

Model

Rated

Voltage

Voltage

Min./Max.

Heater

Element

Watts

Fan

Motor

FLA

Heater

Element

FLA

Total

Unit
FLA

Min.

Circuit

Amp.

Max.

Fuse/

Brkr.

09-12

(1 kW)

208/60/1

197/254

818

0.50

3.93

4.4

5.5

10

230/60/1

197/254

1000

0.50

4.35

4.9

6.1

10

265/60/1

239/291

1000

0.50

3.77

4.3

5.3

10

09-12

(2 kW)

208/60/1

197/254

1636

0.50

7.86

8.4

10.5

15

230/60/1

197/254

2000

0.50

8.70

9.2

11.5

20

265/60/1

239/292

2000

0.50

7.55

8.1

10.1

15

15-18

(3 kW)

208/60/1

197/254

2454

0.69

11.80

12.5

15.6

25

230/60/1

197/254

3000

0.69

13.04

13.7

17.2

30

265/60/1

239/292

3000

0.65

11.32

12.0

15.0

25

10/5/10

PSC Motors

ECM Motors

Model

Rated

Voltage

Voltage

Min./Max.

Heater

Element

Watts

Fan

Motor

FLA

Heater

Element

FLA

Total

Unit
FLA

Min.

Circuit

Amp.

Max.

Fuse/

Brkr.

09-12

(1 kW)

208/60/1

197/254

818

2.45

3.93

6.4

8.0

10

230/60/1

197/254

1000

2.60

4.35

7.0

8.7

15

265/60/1

239/291

1000

2.50

3.77

6.3

7.8

10

09-12

(2 kW)

208/60/1

197/254

1636

2.45

7.86

10.3

12.9

20

230/60/1

197/254

2000

2.60

8.70

11.3

14.1

25

265/60/1

239/292

2000

2.50

7.55

10.1

12.6

20

15-18

(3 kW)

208/60/1

197/254

2454

2.45

11.80

14.3

17.8

30

230/60/1

197/254

3000

2.60

13.04

15.6

19.6

35

265/60/1

239/292

3000

2.50

11.32

13.8

17.3

30

Always refer to unit nameplate data prior to installation.

10/5/10

Model

CFM

Low Speed

High Speed

09

300

350

12

300

350

15

450

500

18

450

500

Factory settings are in Bold
Air fl ow values are with dry coil and standard fi lter.

For wet coil performance fi rst calculate the face velocity of the air coil (Face Velocity [fpm] = Airfl ow [cfm]
/ Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by
0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg.

ECM Motors

PSC Motors

Model

CFM

Low Speed

Medium Speed

High Speed

09

300

325

400

12

300

325

400

15

350

450

600

18

350

450

600