16

NSKW INSTALLATION MANUAL

NSKW Control Box

Transformer

Run Capacitor

(Single Phase Only)

Ground Lug

Load Pump Relay

Terminal Board

Power Block

Terminal Power Strip

Optional IntelliStart

®

(Single Phase Only)

Compressor Contactor

Power Block

(IntelliStart Only)

Source Pump Relay

Reversing Valve Relay
(Reversible Units Only)

Electrical Data

NOTES: *LRA with optional IntelliStart installed

Type D MCB recommended

Model

Rated

Voltage

Voltage

Min/Max

Compressor

Load

Pump

FLA

Source

Pump

FLA

Total

Unit

FLA

Min

Circ

Amp

Max

Fuse/

HACR

MCC

RLA

LRA

LRA*

06

220-240/50/1

198/264

17.0

10.9

58.0

20.0

1.5

4.5

16.9

19.6

30

380-420/50/3

342/462

7.0

4.5

26.0

-

-

-

4.5

5.6

10

08

220-240/50/1

198/264

27.0

17.3

97.0

34.0

1.5

4.5

23.3

27.6

40

380-420/50/3

342/462

10.0

6.4

45.0

-

-

-

6.4

8.0

10

12

220-240/50/1

198/264

31.5

20.2

126.0

44.0

1.5

4.5

26.2

31.2

50

380-420/50/3

342/462

12.1

7.8

51.5

-

-

-

7.8

9.8

15

17

220-240/50/1

198/264

45.0

29.0

130.0

46.0

1.5

4.5

35.0

42.3

70

380-420/50/3

342/462

19.0

12.2

87.0

-

-

-

12.2

15.3

25

9/26/11