Antifreeze correction, Nskw installation manual – WaterFurnace Envision Hydronic User Manual

Page 39

Advertising
background image

39

NSKW INSTALLATION MANUAL

Catalog performance can be corrected for antifreeze use. Please use the following table and note the example given.

Antifreeze Correction

Antifreeze Type

Antifreeze %

by wt

Heating

Cooling

Pressure

Drop

Load

Source

Load

Source

EWT - °C

26.7

-1.1

10.0

32.2

-1.1

Water

0

1.000

1.000

1.000

1.000

1.000

Ethylene Glycol

10

0.990

0.973

0.976

0.991

1.075

20

0.978

0.943

0.947

0.979

1.163

30

0.964

0.917

0.921

0.965

1.225

40

0.953

0.890

0.897

0.955

1.324

50

0.942

0.865

0.872

0.943

1.419

Propylene Glycol

10

0.981

0.958

0.959

0.981

1.130

20

0.967

0.913

0.921

0.969

1.270

30

0.946

0.854

0.869

0.950

1.433

40

0.932

0.813

0.834

0.937

1.614

50

0.915

0.770

0.796

0.922

1.816

Ethanol

10

0.986

0.927

0.945

0.991

1.242

20

0.967

0.887

0.906

0.972

1.343

30

0.944

0.856

0.869

0.947

1.383

40

0.926

0.815

0.830

0.930

1.523

50

0.907

0.779

0.795

0.911

1.639

Methanol

10

0.985

0.957

0.962

0.986

1.127

20

0.969

0.924

0.929

0.970

1.197

30

0.950

0.895

0.897

0.951

1.235

40

0.935

0.863

0.866

0.936

1.323

50

0.919

0.833

0.836

0.920

1.399

WARNING: Gray area represents antifreeze concentrations greater than 35% by weight and should
be avoided due to the extreme performance penalty they represent.

Advertising