Operating parameters, Nskw installation manual, Heating mode – WaterFurnace Envision Hydronic User Manual

Page 38: Cooling mode

Advertising
background image

38

NSKW INSTALLATION MANUAL

Operating Parameters

Heating Mode

Entering

Load Temp (°C)

Entering

Source Temp (°C)

Suction

Pressure (kPa)

Discharge

Pressure (kPa)

Superheat

(°C)

Subcooling

(°C)

15

-15

358-462

1344-1565

4-9

3-8

0

462-565

1434-1620

4-8

3-8

10

655-779

1489-1689

4-8

3-7

20

855-993

1551-1758

4-11

3-8

30

986-1151

1586-1896

8-14

4-7

25

-15

372-476

1951-2179

4-9

4-8

0

476-579

2020-2227

6-7

4-10

10

676-862

2082-2310

7-8

4-9

20

834-1020

2144-2386

8-10

4-9

30

993-1234

2199-2503

8-14

4-9

35

-15

386-490

2544-2792

4-6

3-8

0

531-586

2606-2834

6-7

4-8

10

441-869

2675-2930

7-8

4-8

20

848-359

2744-3020

8-10

2-7

30

1020-1317

2813-3116

8-12

2-7

50

-15

407-510

3137-3413

4-10

2-9

0

510-600

3199-3447

3-9

3-9

10

731-883

3268-3551

3-9

3-8

20

862-1076

3344-3654

3-9

2-8

30

operation not recommended

9/26/11

Cooling Mode

Entering

Load Temp (°C)

Entering

Source Temp (°C)

Suction

Pressure (kPa)

Discharge

Pressure (kPa)

Superheat

(°C)

Subcooling

(°C)

10

0

593-683

931-1103

7-12

1-8

10

634-738

1317-1475

6-11

2-8

20

676-793

1710-1848

3-8

3-9

30

696-820

2310-2530

3-8

4-9

45

724-841

2930-3206

4-9

6-11

20

0

614-731

903-1124

8-11

2-3

10

710-862

1338-1538

6-8

3-5

20

814-986

1772-1882

6-8

5-7

30

862-1041

2372-2627

4-7

7-8

30

0

634-779

883-1145

8-11

2-3

10

793-986

1358-1606

6-8

3-5

20

889-1089

1834-2027

6-8

5-7

30

1034-1158

2441-2723

4-7

7-8

45

0

662-834

862-1172

31-36

1-11

10

876-1110

1379-1675

23-29

2-4

20

1089-1379

1896-2172

12-21

4-11

30

operation not recommended

NOTE: Operating parameters based on normal conditions with 0.19 L/s per kW output for the load and source.

9/26/11

Advertising