Electrical data, Blower performance data, Blower performance data electrical data – WaterFurnace Envision Low Sill User Manual

Page 18

Advertising
background image

18

ENVISION LOW SILL CONSOLE INSTALLATION MANUAL

Blower Performance Data

Electrical Data

Model

Rated

Voltage

Voltage

Min/Max

Compressor

Blower

Motor

FLA

Total

Unit
FLA

Min

Circ

Amp

Max

Fuse/
HACR

MCC

RLA

LRA

09

115/60/1

104/127

12.5

8.0

50.0

1.5

9.5

11.5

15

208-230/60/1

187/253

6.4

4.1

21.0

0.6

4.7

5.7

10/15

265/60/1

238/292

6.7

4.3

22.0

0.6

4.9

6.0

10/15

12

115/60/1

104/127

14.8

9.5

50.0

1.5

11.0

13.4

20

208-230/60/1

187/253

7.7

4.9

25.0

0.6

5.5

6.7

10/15

265/60/1

238/292

7.0

4.5

22.0

0.6

5.1

6.2

10/15

15

208-230/60/1

187/253

9.2

5.9

29.0

2.6

8.5

10.0

15

265/60/1

238/292

7.8

5.0

28.0

2.5

7.5

8.7

10/15

18

208-230/60/1

187/253

10.4

6.7

33.5

2.6

9.3

11.0

15

265/60/1

238/292

8.7

5.6

28.0

2.5

8.1

9.5

15

HACR circuit breaker in USA only

6/10/13

Model

CFM

Low Speed

High Speed

09

260

300

12

300

340

15

375

450

18

450

600

Air fl ow values are with dry coil and standard fi lter.
For wet coil performance, fi rst calculate the face velocity of the air coil
(face velocity (fpm) = airfl ow (cfm) / face area (sq ft))