Wiring schematics cont, Test mode control timing table, Operational logic table – WaterFurnace Envision Low Sill User Manual

Page 25: Led display mode table, Logic board dip switch settings

Advertising
background image

25

ENVISION LOW SILL CONSOLE INSTALLATION MANUAL

Wiring Schematics cont.

CC Relay

Blower Relay

CC

CCG

C
C

R
R

Blower

Blower COM

R

C

Y

O

G

LO

ES

P3

P1

SW1

Microprocessor

Logic Control

17P529A01

P2

6

1

7

2

8

3

9

4

10

5

Versatec Logic Board Physical Layout

Normal Mode Control Timing Table

Blower off delay

Compressor on delay

Compressor short cycle delay

Minimum compressor on time

High pressure fault recognition delay

Low pressure fault recognition delay

Condensate overflow fault recognition delay

Low pressure fault bypass delay

Freeze sensing fault bypass delay

Power on delay

Freeze sensing fault recognition delay

30 seconds

10 seconds

5 minutes

2 minutes (except for fault condition)

Less than 1 second

30 seconds

30 seconds

30 seconds

2 minutes (for first fault only, 0 sec after)

2 minutes (for first fault only, 0 sec after)

5 minutes

Test Mode Control Timing Table

Blower off delay

Compressor on delay

Compressor short cycle delay

Minimum compressor on time

High pressure fault recognition delay

Low pressure fault recognition delay

Condensate overflow fault recognition delay

Low pressure fault bypass delay

Freeze sensing fault bypass delay

Power on delay

Freeze sensing fault recognition delay

Fault off time

5 seconds

2 seconds

15 seconds

5 seconds (except for fault condition)

Less than 1 second

30 seconds

30 seconds

30 seconds

0 seconds

0 seconds

15 seconds

5 minutes

Operational Logic Table

Mode

Htg

Clg

Inputs

Blower

Comp

RV

Y

Y,O

Blower

G

ON

ON

ON

OFF

ON

ON

OFF

ON

OFF

SW1-4 On, SW2 Off
Drain pan overflow lockout
FS thermistor (loop<=15°F, well<=30°F) lockout
High pressure lockout
Low pressure lockout
Not used
Microprocessor malfunction*
Not Used
SW2 status (Off=down position,On=up position)

Drain

Water Flow

High Press

Low Press

Air Flow

Status

DHW Limit

HWD

LED

Normal Display Mode

SW1-4 On, SW2 On

Drain pan overflow

FS thermistor (loop<=15°F, well<=30°F)

High pressure

Low pressure

Not used

Not used

Not used

SW2 in the On position

Current Fault Status

SW1-4 Off, SW2 Off

Y

G

O

ES

Not Used

Not Used

Not Used

SW2 in the Off position

Inputs

Compressor

Blower

O

ES

Not Used

Not Used

Not Used

SW2 in the On position

Outputs

Diagnostic Modes

SW1-4 Off, SW2 On

Drain

Water Flow

High Press

Low Press

Air Flow

Status

DHW Limit

HWD

LED

LED Display Mode Table

*Flashing Status light indicates microprocessor is functioning properly. Solid "on" indicates a
microprocessor malfunction.

Switch

OFF

ON

SW1 - 1

SW1 - 2

SW1 - 3

SW1 - 4

SW1 - 5

SW2

Test Mode - Selected timings sped up to
facilitate troubleshooting
Loop - Closed loop freeze sensing
setting (15°F)

IO Display* - Enables Input/Output display
on external LED board*

Commercial - Enables NS features when
TA32U02 thermostat is used

Split Mode – Dual-Speed-Compressor
and with No blower
OFF* - Normal or Input display mode
activated

Normal Mode - Standard timings

Well - Open loop freeze sensing setting
(30°F)

Normal* - Unit status display

Normal - Standard thermostat operation

Normal - Single-Speed Compressor
with blower
ON* - Current fault or Output display
mode activated

* Refer to LED Display Mode table for position of SW1-4 and SW2

Logic Board DIP Switch Settings

Versatec Control Board

Advertising