Operating parameters, Operating limits – WaterFurnace Envision Low Sill User Manual

Page 37

Advertising
background image

37

ENVISION LOW SILL CONSOLE INSTALLATION MANUAL

Operating Parameters

Entering Water

Temp °F

Water Flow

gpm/ton

Cooling

Suction Pressure

psig

Discharge

Pressure psig

Superheat

Subcooling

Water Temp Rise

°F

Air Temp Drop

°F DB

30

1.5

100 - 115

170 - 190

17 - 26

10 - 14

18 - 22

20 - 30

3.0

115 - 125

150 - 170

20 - 29

7 - 11

8 - 10

20 - 30

50

1.5

133 - 148

225 - 245

8 - 11

7 - 11

18 - 22

20 - 30

3.0

129 - 144

185 - 205

8 - 11

6 - 10

8 - 10

20 - 30

70

1.5

139 - 154

300 - 320

6 - 10

6 - 10

18 - 22

18 - 26

3.0

137 - 152

250 - 270

6 - 10

6 - 10

8 - 10

18 - 26

90

1.5

143 - 158

360 - 380

6 - 10

6 - 10

18 - 22

18 - 26

3.0

141 - 156

330 - 350

6 - 10

6 - 10

8 - 10

18 - 26

110

2.3

143 - 158

360 - 380

6 - 10

6 - 10

18 - 22

18 - 22

3.0

141 - 156

440 - 460

6 - 10

6 - 10

8 - 10

18 - 22

Entering Water

Temp °F

Water Flow

gpm/ton

Heating

Suction Pressure

psig

Discharge

Pressure psig

Superheat

Subcooling

Water Temp Drop

°F

Air Temp Rise

°F DB

30

1.5

73 - 79

305 - 330

7 - 13

7 - 11

7 -10

20 - 26

3.0

79 - 85

315 - 345

7 - 13

7 - 11

3 - 6

20 - 26

50

1.5

103 - 109

330 - 370

7 - 13

7 - 11

8 - 11

22 - 32

3.0

115 - 130

350 - 380

7 - 13

7 - 11

4 - 7

22 - 32

70

1.5

145 - 155

375 - 410

7 - 13

7 - 11

11 - 14

28 - 38

3.0

155 - 165

415 - 435

10 - 14

7 - 11

7 - 10

35 - 45

90

1.5

170 - 185

435 - 470

11 - 18

7 - 11

8 - 11

42 - 50

3.0

174 - 190

465 - 500

11 - 18

7 - 11

8 - 11

42 - 50

110

2.3

3.0

NOTES: Cooling performance based on entering air temperatures of 80°F DB, 67°F WB.

6/20/11

Heating performance based on entering air temperature of 70°F DB.

Operating Limits

Operating Limits

Cooling

Heating

(°F)

(°C)

(°F)

(°C)

Air Limits

Min. Ambient Air

45

7.2

45

7.2

Rated Ambient Air

80

26.7

70

21.1

Max. Ambient Air

100

37.8

85

29.4

Min. Entering Air

50

10.0

40

4.4

Rated Entering Air db/wb

80.6/66.2

27/19

68

20.0

Max. Entering Air db/wb

110/83

43/28.3

80

26.7

Water Limits

Min. Entering Water

30

-1.1

20

-6.7

Normal Entering Water

50-110

10-43.3

30-70

-1.1

Max. Entering Water

120

48.9

90

32.2

NOTE: Minimum/maximum limits are only for start-up conditions, and
are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependant upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
levels, the other two factors must be at the normal level for proper and
reliable unit operation.