ENVISION LOW SILL CONSOLE INSTALLATION MANUAL

Compressor Minimum On Delay

The compressor minimum on delay will ensure that the

compressor output is enabled for a minimum of (2)

minute each time the compressor output is enabled. This

will apply in every instance except in the event the high

pressure switch is tripped or emergency shutdown then the

compressor output will be disable immediately.

Compressor Short Cycle Delay Time

The compressor short cycle time delay will ensure

that the compressor output will not be enabled for a

minimum of (5) minutes after it is disabled. This allows

for the system refrigerant pressures to equalize after the

compressor is disabled.

Heating Cycle

On a call for heating, the blower enable output and

accessory output 2 will turn on immediately after the

random start delay timer has been satisfied. If the

compressor short cycle time delay has been satisfied,

the compressor will turn on after the blower enable and

accessory output 2 are on and the fixed compressor start

delay timers have been satisfied.

Cooling Cycle

On a call for cooling, the blower enable output and

accessory output 2 will turn on immediately after the

random start delay timer has been satisfied. If the

compressor short cycle time delay has been satisfied,

the compressor will turn on after the blower enable and

accessory output 2 are on and the fixed compressor start

delay timers have been satisfied.

MUI Alarm History Reporting

If a fault occurs the fault will be recorded in history for

display on the medium user interface in the History Menu.

Each fault type will be displayed in the history menu with

a number between 0 and 3. A reading of 3+ will mean

that fault has occurred more than three times in the past.

The history menu can be cleared with a power cycle only.

Alarm date and time are not included in the history.

Inputs and Outputs Configuration

Field Selectable Options

Freeze Detection Limit Set Point (BI-5)

The freeze detection limit set point input allows you to

adjust the freeze detection limit set point (AI-5). When the

jumper is installed on BI-5 (Wire #24) the freeze detection

limit set point is factory set for 30°F. When the jumper on

BI-5 (Wire #24) is removed the freeze detection limit set

point will be 15°F.

Accessory Outputs (BO-7 and BO-8)

Accessory Output 1 will be energized 90 seconds prior to

the compressor output being energized. Accessory Output

2 will be energized with the fan output (BO-1). When

the corresponding compressor output is turned off the

accessory output will be deactivated immediately. These

outputs are selectable for normally open or normally closed

operation through the Medium User interface or through

the Building Automation System.

Control Accessories

Zone Sensors

• TAXXJ02 Room Command Module

• TAXXA04 LCD Room Command Module

• A99

Sensor

MUI (LCD User interface) for diagnostics

and commissioning.

• MUIK3 - Panel Mount, Portable

• MUIK4 - Wall Mount

Controls cont.

Input Name

Input

Output Name

Output

Zone Temp 1

AI 1

Fan Enable

BO1

Relative Humidity Input

AI 2

Comp – Low Capacity

BO2

Condensate Level

AI 3

Reversing Valve

BO3

Universal Temp Input

AI 4

Comp – Full Capacity

BO4

Water Coil Low Temperature Limit

AI 5

Network Output/EH Output

BO5

Warm/Cool Adjust and Temp Occ

AI 6

Alarm

BO6

Accessory 1 Output

BO7

Occupied

BI 1

Accessory 2 Output

BO8

Emergency Shutdown

BI 2

Network Controlled Output

B09

Stage 1 Low Pressure

BI 3

Network Viewable Input 1

BI 4

ECM2 Fan

PWM1

Water Coil Low Temp Limit Set Point

BI 5

Network Controlled Output

PWM2

Network Viewable Input 2

BI 6

Thermostat Y1

BI 7

Thermostat Y2

BI 8

Thermostat O

BI 9

Thermostat G

B10

Stage 1 High Pressure

BI11

Compressor Proving

BI12

XP10 Expansion Card

Input Name

Input

Output Name

Output

Unused

AI 1

Unused

BO 1

Unused

AI 2

Unused

BO 2

Unused

AI 3

Unused

BO 3

Unused

AI 4

Unused

BO 4

SINGLE and DUAL STAGE WATER-TO-AIR