4�- OPERATION

The

CVM-C5 is a power analyzer in four quadrants (consumption and generation).

90º

180º

-90º

Capacitive

Capacitive

Inductive

Inductive

Generation

Power

Consumption

Power

Single-phase

Three-phase

Single-phase

Single-phase

Single-phase Three-phase

Three-phase

Three-phase

k

k

k

k

k

k

k

k

k

k

k

k

k

k

k

k

k

k

k

k

Figure 10: Four quadrants of CVM-C5�

4.1.- MEASURING PARAMETERS

The unit displays the electrical parameters shown in

Table 3

.

Table 3: CVM-5 measuring parameters�

Parameter

Units

Maximum

value

Minimum

value

Phase – neutral voltage

Vph-n

9999

10.0

Phase-phase voltage

Vph-ph

9999

10.0

Current

A

9999

0.05

Frequency

Hz

65

45

Active Power

kW

9999

0.01

Inductive Reactive Power

kvarL

9999

0.01

Capacitive Reactive Power

kvarC

9999

0.01

Apparent Power

kVA

9999

0.01

Power factor

PF

-0.99

0.99

Cos φ

φ

-0.99

0.99

Total Active Energy Consumed Tariff 1

kWh

999999

000.000

Total Active Energy Generated Tariff 1

kWh

999999

000.000

Inductive Reactive Energy Consumed Tariff 1

kvar

L

h

999999

000.000

Inductive Reactive Energy Generated Tariff 1

kvar

L

h

999999

000.000

Capacitive Reactive Energy Consumed Tariff 1

kvar

c

h

999999

000.000

Capacitive Reactive Energy Generated Tariff 1

kvar

c

h

999999

000.000

Total Apparent Energy Tariff 1

kVAh

999999

000.000

Total Active Energy Consumed Tariff 2

kWh

999999

000.000

Total Active Energy Generated Tariff 2

kWh

999999

000.000

Inductive Reactive Energy Consumed Tariff 2

kvar

L

h

999999

000.000

Inductive Reactive Energy Generated Tariff 2

kvar

L

h

999999

000.000

Capacitive Reactive Energy Consumed Tariff 2

kvar

c

h

999999

000.000

Capacitive Reactive Energy Generated Tariff 2

kvar

c

h

999999

000.000

17

Instruction Manual