CIRCUTOR CVM-BD Series User Manual

Page 21

Advertising
background image

-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 20


- If you select “SET PAGE YES” , you can program the desired parameters in this
page :

xx A1
xx A2
xx A3

Parameter code ( set-up ) / Parameter symbol


SET-UP :
- "max" key : Allows us modifying the value of the blinking digit. Each time it is
pressed the value is increased.

- "min" key : Allows us the validation of the blinking digit and going to the next one.

Each display has two digits to select the desired parameters among the ones in the
attached code chart:

Parameter

Symbol

phase L1

Code

Symbol

phase L2

Code

Symbol

phase L3

Code

Single voltage

V 1

01

V 2

07

V 3

13

Current

A 1

02

A 2

08

A 3

14

Active power

kW 1

03

kW 2

09

kW 3

15

Inductive power

kvarL 1

04

kvarL 2

10

kvarL 3

16

Capacitiva power

kvarC 1

05

kvarC 2

11

kvarC 3

17

Power factor

PF 1

06

PF 2

12

PF 3

18

Three phase single voltage Vav III

19

Frequency

Hz

25

Three phase current

Aav III

20

Three ph. apparent power kVA III

26

Three phase active power kW III

21

Ph-Ph voltage L1- L2

V 12

27

Three. ph. inductive power. kvarL III

22

Ph-Ph voltage L2 - L3

V 23

28

Three ph. capacitive power

kvarC III

23

Ph-Ph voltage L3 - L1

V 31

29

Three ph. power factor.

PF III

24

Three ph. Ph-Ph voltage

Vc III

30

Advertising