-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 28

1.- Output calculation:

Resolution = 20

Zero .

F. scale - offset

Offset & f. scale

= defined by the

user
Zero

= 0 mA or 4 mA

MA = (( F. scale - offset ) x Resolution) + Zero

MV = mA x ohms

mV

(100 ohms)

= mA x 100

-

Maximum load is:

CVM-BD-420-4: ................400 Ω
CVM-BD-420-8: ................300 Ω

-

The maximum allowable offset is a value equal to the 90% of the full scale.

-

Output of the power factor parameter ( P.F.):

0/4 mA ----------------------------

-------------------------20 mA

+0.00 Ind. 1.00 Cap. – 0.00




2.- Default full scale:

Parameter

Condition

Full scale ( 20 mA )

Voltages

Primary < 500

Primary x 500 /secondary

(V)

Primary > 500

Voltage primary

Currents (A)

Current primary

Powers

For one phase

voltage primary x current primary / 1000

(kW)

Three phase value

voltage primary x current primary x 3 / 1000

Frequency (Hz)

65

P.F.

0.00