CIRCUTOR CVM-BD Series User Manual

Page 6

Advertising
background image

-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 5


You can select:

a) The parameter to be controlled (it can measure active power kW,

apparent power kVA or three phase average current AIII).

b) The demand period (1 to 60 min.).


This power demand function works with sliding window : shows the accumulated
demand over the last period from "now".

---------------------------------------------------------------------------------------------

The CVM-BD-420-.. is a 4 quadrant analyzer, that is, this can automatically

detect the energy sign:

Example of the
phase difference
between voltage
and current


Active power
kW or kW.h


Reactive power
kvar or kvar.h

P.F.

30º

kW +

kvar L +

+

300º

kW +

kvar C +

--

210º

kW --

kvar L --

+

120º

kW --

kvar C --

--


Advertising
This manual is related to the following products: