CIRCUTOR QNA-P Series User Manual

Page 11

Advertising
background image

Page no.

10

5.2.-

QNA-412 analyzer start up.

Before connecting the equipment to the mains please bear in mind the

following points:

1) Supply system voltage:

Voltage:

63 – 520 V AC.

Frequency: 50... 60 Hz.

2) Earth: The equipment must have the earthing cable connected. If it is not

attached, some of the equipment's protection will become ineffective.

3) Maximum current in the voltage measurement circuit: 500 V AC. between phase

and common:

4 wire configuration: 500 V AC Neutral-phase / 866 V AC. phase-phase.
3 wire configuration: 500 V AC. phase-phase.

4) Maximum measurement current: According to CLAMPS USED. In / 2 V AC.

5) Maximum measurement current: According to CLAMPS USED. In / 2 V AC.

6) Equipment consumption: 16 W.

7) Operating conditions:

• Operating temperature: 0º to 50º C.

• Operating humidity: 25% to 75 % RH.

8) Safety: Designed for category III installations according to EN 61010.

Points to check during installation:

8) Check that the earth has been connected to avoid interference to the equipment.

Not attaching the earth reduces the effectiveness of the QNA-412's protection.

9) Check the power measurements and their sign (Check the polarity of the current

transformers).

10) Check the QNA-412 analyzer setting.

Please note

A symptom of poor installation or wrong setting is the measurements flashing

on the display. The causes may be:

− The equipment has detected an event. This may mean that there has

actually been an event on the line (correct installation) or that the pre-set
nominal voltage does not match that of the system.

− If dashes appear on the balance screen: it means that the sequence of

the phase turn is wrong.