CIRCUTOR EMK Series User Manual

Page 17

Advertising
background image

EMK

series

Instructions Manual M98118701-01-12A 17

Table 7-4.- Nominal consumption of the capacitor steps, depending on its power

POWER

CURRENT

230 V

400 V

I

n

I

n

2.5 kvar

6.28 A

3.6 A

5 kvar

12.56 A

7.2 A

7.5 kvar

18.85 A

10.8 A

10 kvar

25.12 A

14.4 A

12.5 kvar

31.41 A

18 A

15 kvar

37.7 A

21.6 A

20 kvar

50.24 A

28.8 A

25 kvar

62.82 A

36 A

30 kvar

75.4 A

43.2 A

40 kvar

100.48 A

57.6 A

50 kvar

125.64 A

72 A

60 kvar

150.8 A

86.4 A

70 kvar

175.92 A

101.1 A

80 kvar

200.96 A

115 A

NOTES:

When the consumption of the steps is 25% less than stated in and the voltage is within the
tolerance limits, this is a sign of degradation of the capacitors. These must be replaced with a
suitable spare part if these symptoms are detected in a step.

When the consumption of the steps is 10% more than stated in, this can be caused by the
presence of resonances. If this is detected, measure the THD(V) of network voltage (should be
below 5%).


7.3.3

Regulator Checkings

Refer to the manual of the specific regulator used in the capacitor bank. This
manual is always supplied with the capacitor bank.

Make sure that there are no damaged segments on the display (abnormal brightness).

Make sure that regulator's keyboard is working properly:

- Enter Setup and check the adjusted values
- Force the manual connection and disconnection of a step.

7.4

Environmental Conditions:

Check that the maximum environmental conditions listed in section 4.3 are observed

8

GUARANTEE,


CIRCUTOR guarantees its products against any manufacturing defect for two years after
equipment delivery.

CIRCUTOR will repair or replace any defective factory product returned during the guarantee
period.

No returns will be accepted and no unit will be repaired or replaced if it is not
accompanied by a report indicating the defect detected or the reason for the return.