4.2

Electrical features

-

Operating voltage and nominal frequency:

U

n

/ f , listed on the label

-

Design voltage:

U

n

+ 10% (440 V for 400 V equipment)

-

Nominal power and distribution of steps:

Q

n

and composition, (see label)

-

Total loss:

Typical 1 W/kvar

-

Residual discharge voltage:

75 V after 3 minutes

-

Overload capacity:

1.3 I

n

in all items

-

Auxiliary voltage:

U

aux

, listed on the label.

NOTE: In general, use a 1.5 mm

2

cable to supply external power.

If “Internal” , is marked in the label , this circuit does not require external power.

-

Current Transformer:

Secondary Winding 5 A ,

(Transformer I

n

/5 A)

NOTE: Minimum cable section 2.5 mm

2

.

-

Compliance with Standards

UNE EN 61921 and EN-61642

-

Protection elements:

NH Fuses

, gL curve, minimum calibre 1.5 I

n

)

-

Capacitor features:

Capacity tolerance:

± 10%

Insulation level from earth:

3 kV /50 Hz

Impulse test:

15 kV , ray type wave 1.2/50 µs

Protection elements:

Internal fuses and over-pressure system

Compliance with Standards

EN 60831

4.3

Environmental Features

-

Capacitor max. temperature

Category C in accordance with EN 60831-1

Maximum for 1h

50ºC

24h average

40ºC

Annual average

30ºC

-

Cabinet ventilation

For outdoor t

amb

> 30ºC, forced ventilation

must be used for the cabinet

-

Maximum relative humidity:

80%

-

Altitude:

1000 m

(For higher altitudes, use always

forced ventilation)

4.4

Mechanical features

-

Protection degree:

Marked on the label:

-

Paint

Oven dried epoxy type

-

Standard colours

RAL 7035 Grey ; RAL 3005 Wine Red

4.5

External dimensions and weights.


Model

Dimensions (mm)

Max.

weight

(kg)

Width

Height

(*)

Depth

EMK4

880

1805

575

172

EMK6

1180

1805

575

186

EMK8

1530

1805

575

200

EMK12

2360

1805

575

371


(*)

Maximum dimensions