Advanced programming – CP Electronics VITP-MWS3A User Manual

Page 6

Advertising
background image

6

Parameter Name Default Value Range / Options Description

UHS5 UNLCDHS

Detector Parameters

Walk Test LED

Off

On or Off

When set to On this causes a red LED to flash on the sensor when it detects

movement. Use this feature to check for adequate sensitivity levels.

 

Time Out
(Time adjustment)

20 minutes

0-99 minutes

Once the detector is turned on, this value sets how long the lights will stay on once

movement has ceased. Select 0 for 10 second delay – use for commissioning only.

 

Sensitivity On

9

1 (min) to 9 (max)

Sensitivity level for detecting movement when the detector is already on. *UHS5

sets Sensitivity On and Off to the same value.

* 

Sensitivity Off

9

1 (min) to 9 (max)

Sensitivity level for detecting movement when the detector is off. *UHS5 sets

Sensitivity On and Off to the same value.

* 

Lux time

0

0 (disabled)
1-99 minutes

If the detector measures the lux level and decides that the output needs switching
on or off as a consequence, the lux time must elapse first. If at any time during the
timed delay the lux change reverses then the process is cancelled.

 

Power Up State

On

On or Off

Select No for a 30 second delay on start up. If Yes is selected, there will be no

delay on start up and the detector will always power up detecting.

 

Factory default

-

-

Restores factory default settings

 

User Modes

Raise

-

-

Increase light level. Reverts when occupancy cycle complete.

 

Lower

-

-

Decrease light level. Reverts when occupancy cycle complete.

 

Override On

-

-

If the lights are off, sending the IR command will turn them on immediately and

revert to automatic operation using the manual timeout period.

 

Override Off

-

-

If the lights are on, sending the IR command will turn them off immediately. After

the manual timeout period (described above), the sensor will revert to automatic.

 

Cancel

-

-

Cancels the on or off override, returning the detector to normal operation.

 