7. Specifications and Mechanical Drawings

Inputs...................................................8 x digital (potential-free) contact closure input,
............................................................2 x 8-pin connector Phoenix 3.5 mm
Outputs................................................4 x potential free relay C-NO, 230 V, max. 10 A (resistive load)
............................................................4 x potential free relay NC-C-NO, 230 V, max. 10 A (resistive
............................................................load)
............................................................max. 400W per relay for inductive or capacitive load
............................................................screw-type terminals up to 1.5 mm

2

LED indicators.....................................Power, serial channel activity, status of all relays
Buttons................................................8 x test button for power relay control,
............................................................ACT button for address and bank settings
Insulation strength...............................2.5 kV between power and control circuits
Serial communication..........................RS-485, 5-pin connector Phoenix 3.5 mm
Power supply.......................................230 VAC or 110 VAC, 50/60 Hz, 6 W,
............................................................screw-type terminals up to 1.5 mm

2

Enclosure............................................Plastic DIN rail compatible enclosure
Dimensions..........................................159 x 90 x 58 mm / 6.2” x 3,5” x 2,3” (9 modules 17.5 mm)
Weight.................................................0.5 kg / 1.1 lb
Operating environment........................Temperature 0° to 60° C
............................................................Humidity 10% to 90% non-condensing
Supplied accessories...........................Cable CA0183
............................................................Cable adapter GP0045

All dimensions are in mm.

Important note:

The relay contacts in relayCUE-8 are constructed for resistive load up to 230V/10A. If these
relays are used for the switching of inductive (or capacitive) loads, voltage or power peaks can
occur, which may exceed these parameters even if the load has the stated take-off lower than
230V/10A. We therefore do not recommend using relayCUE-8 for switching inductive or
capacitive loads with take-off higher than 400W.

If you need to switch higher loads, use contactors. Unlike relays, contactors are designed with
features to control and suppress the arc produced when interrupting inductive load currents.
You can then use the relay of the relayCUE-8 unit to control the coil of this contactor.