14

SLT Series

Diagnostics and Troubleshooting

2 ...................... 2 Beams Broken

Definition:

The light guard was triggered when at

least two beams were detected broken.

Status:

RED, fail safe relays off.

Reason(s):

Floating Blank option: set to 4cm mode.
a) If no obstruction is observed, then

light curtain is misaligned.

b) Emitter Pylon is not transmitting.

Cure(s):

Remove all obstructions. If display still

reads 1 or 2, then realign light curtain

with the Floating Blank option in 2cm

mode or the Auto Blank option in OFF/

RESET position (see Installation

Procedure, Page 3).

3 ...................... 3 Beams Broken

Definition:

At least three beams were detected

broken.

Status:

RED, fail safe relays off.

Reason(s):

Floating Blank option: set to 6cm mode.
a) If no obstruction is observed, then

light curtain is misaligned.

b) Emitter Pylon is not transmitting.

Cure:

Remove all obstructions. If display still

reads 1, 2, or 3, then realign light curtain

with Floating Blank option in 2cm mode

or Auto Blank option in OFF/RESET

position (see Installation Procedure,

Page 3).

4 ...................... 4 Beams Broken

Definition:

The light guard was triggered when at

least four beams were detected broken.

Status:

RED, fail safe relays off.

Reason(s):

Floating Blank option: set to 8cm mode.
a) If no obstruction is observed, then

light curtain is misaligned.

b) Emitter Pylon is not transmitting.

Cure(s):

Remove all obstructions. If display still

reads 1, 2, 3, or 4, then realign light

curtain with Floating Blank option in

2cm mode or Auto Blank option in OFF/

RESET position (see Installation

Procedure, Page 3).

5 ...................... Relay Fault: One On / One Off

Definition:

There are two captive contact relays

inside the light curtain of which one is

open and the other is closed. This

condition should never occur because

the system is designed to always

operate both relays together.

Status:

Both the RED and GREEN lights are

on but the output circuit is broken and

the light curtain has failed safe.

Reason(s):

a) Contact on one relay welded

together keeping it closed or other

internal mechanical relay

malfunction.

b) Fault in one of the driver IC’ s

causing either a relay to remain on

or off.

c) Jumper settings on watchdog timer

IC’s are incorrectly set.

d) Fault in one of the two watchdog

timers controlling the driver IC’ s

which require a clock signal of a

period less then 1 mSEC.

e) Fault in the gate chip between the

Master and Slave computers which

allows the Slave computer to

override the Master and turn a relay

on.

f) Error condition exists within one of

the two computers.

g) The two computers disagree on

whether to turn the relays off.

h) Line voltage levels too low to

activate one of the two relays.

Cure(s):

Only reason a) can be checked by user,

all other reasons can only be checked

by authorized trained personnel.

6 ...................... Relay Fault: Both off (should be on)

Definition:

Both relays were detected as OFF

when they were signalled by the

computer to turn on.

Status:

Red light on, fail safe.

Reason(s):

a) Internal mechanical relay problem.
b) Jumpers on watchdog timer IC’ s

are incorrectly set.