WaveWare API-64 Alarm Monitoring User Manual

Page 12

Advertising
background image

(4) Once the system has completed the search process, the "ITEM" field will indicate how many items or
separate events are stored in the data log for the period between the START and END dates and times. The
last (newest) event that occurred during the defined time period will be displayed and is designated "ITEM"
001 of XXX. Use the <PAGE UP> <PAGE DOWN> keys to view each of the logged events, one message
at a time.

PAGE 4-7

(5) Press <F2> to print all of the items which are stored in the DATA LOG for the defined time period. Use
the <ESCAPE> key to stop printing.

Back To Index

API-64RM PROGRAMMING INSTRUCTIONS

This section explains how to set paging functions for the API-64RM remote dial module. The unit is
programmable via any DOS based computer with a communications port. The programming kit supplied
with the API-64RM is required to set the unit up for paging functions. Before you begin you should obtain
the following information from your paging company or system manager and have it available:

(1) The Paging Terminal Telephone Number (for an IXO Port). (This number is supplied by the paging
company or system manager for sending alphanumeric messages from a PC or a dedicated alphanumeric
message entry device via the telephone system)

(2) The Paging Terminal Password. Some paging companies/systems require a password. Most do not and
this section of the programming menu may be left blank.

PROGRAMMING NOTES:

1. When Programming the Terminal Number, the @ character may be inserted to provide a one second
pause. You may wish to use this if you must dial 9 before dialing a number outside of your facility or
organization. A pause of a few seconds will leave enough time to obtain dial tone before the API-64RM
begins its dialing sequence.

Example 9@@@5551111

2. If you are reprogramming a previously programmed unit use the backspace key to erase previously
programmed data.

4. When you reach the end of the allowed data field when programming one of the parameters the cursor
will freeze, and no key strokes will be echoed back.

Back To Index

PROGRAMMING PROCEDURE

1. Start the computer that is to be used for the programming.

2. Connect the serial cable supplied with the Programming Kit from the Program/RS232 Port on the API-
64RM to a communications port on the PC.

3. Insert the Programming Disk into a floppy drive.

4. At the DOS prompt type A: or B: ( the location of the programming disk) and press <ENTER>.

5. At the A:\> or B:/> prompt type "TERM 1 1200" or "TERM 2 1200" and then press <ENTER>. The
number one or two in this command indicates the COM PORT that the programming cable is connected to.
The screen should now read:

Monitor Technologies Inc

Programming System REV 1.1

API-64RM

Type <CTRL> N to exit program