Sensor connections, Ez zone/auto-zone upgrade 21, Figure 8: new az zone manager sensor wiring – Auto-Zone Control Systems EZ-Zone to Auto-Zone Upgrade Guide (Version 01C) User Manual

Page 21

Advertising
background image

EZ Zone/Auto-Zone

Upgrade

21

Sensor Connections

Figure 8: New AZ Zone Manager Sensor Wiring

ANALOG

INPUTS

+V

+V

1

2

3

4

5

6

7

8

G

G

PRESSURE

SENSOR

+5V

SIG

GND

TB12

Static

Pick-up

Static

Pressure

Sensor

Splice As

Required

LO

HI

Red

Blk

Grn

Supply Air

Sensor

To Bypass

Actuator Feedback

+

+

+

+

R9

R10

C

4

C4

R8

AUX1

ANALOG

OUTPUTS

A2

G

TB5

TB4

TB3

A1

N.O.

CONTACTS

EXHAUST

GND

GND

AUX3

AUX2

D3
D4
D5
D6
D8

D2

PR
ESSU

R

E

SE
N

SO
R

JAC
K

+5V

R7

INPUTS

OAT

RAT

+12V

SAT

ANALOG

GND

SIG

TB1

PJ1

Return Air Temp.

Sensor

Supply Air Temp.

Sensor

Outdoor Air Temp.

Sensor

Static

Pick-up

Static

Pressure

Sensor

Splice As

Required

LO

HI

Figure 7: Existing EZ Zone Master Controller Sensor Wiring

The EZ Zone Master Controller sensor connec-
tions are located on the right side of the board.
Only a supply air temperature sensor and the
bypass actuator feedback are connected here.

The Auto-Zone Zone Manager includes termi-
nals for connecting the following sensors:

• Supply Air Temperature

• Return Air Temperature

• Outside Air Temperature

The terminals are marked SAT, RAT, and OAT
for ease of wiring. Auxiliary input terminals
AUX1, AUX2 and AUX3 are used for Econo-
mizer Disable, Dirty Filter Alarm and Forced
Occupied Mode. Bypass damper feedback has
been relocated (see next page).