Honeywell economizer actuators, Ez zone/auto-zone upgrade 23, Zone manager – Auto-Zone Control Systems EZ-Zone to Auto-Zone Upgrade Guide (Version 01C) User Manual

Page 23

Advertising
background image

EZ Zone/Auto-Zone

Upgrade

23

Honeywell Economizer Actuators

TR

T1

P

P1

24VAC

24VAC

Zone Manager

Wiring OE266-01 Actuator Interface Module Kit To Zone Manager (Basic & Plus Systems)

Installing MS000204 Interface Module To Honeywell M7415 Or 7405 Actuator

Q769C1007 Interface Module

(WM # MS002004)

Warning:

!

An Isolation Transformer

Must Be Used For Connection To

Actuator Or Serious Damage Will

Result

+

TR1

T

-

A1

G

TB2

A2

G

OUTPUTS

ANALOG

A1

N.O.

CONTACTS

EXHAUST

AUX3

GND

GND

AUX2

AUX1

ANALOG

SAT

OAT

RAT

INPUTS

+12V

Honeywell Series M7415

Or M7405 Actuator

24

VA

C

24

VA

C

T1

T1

TR

TR

T

T

P
P1

TR1

TR1

SENSOR

SENSOR

MIN

POSN

M7415A1014

025-26250

M7415A1014

025-26250

24 VAC - Isolation Transformer

(WM # WP000019)

Honeywell M7415 Actuator

Without Interface Module

Honeywell M7415 Actuator With

Q769C1007 (WM # MS000204)

Interface Module Installed

Place Interface Module On

Terminals P1 and P

Figure 11: Honeywell Economizer Actuators Wiring Information

When the HVAC units that are being upgraded to
the Auto-Zone system are equipped with either the
Honeywell M7415 or M7405 economizer actua-
tors, an interface module and a isolation transformer
are required in order to connect and use the econo-
mizer outputs on the Auto-Zone system. The inter-
face module converts the Honeywell actuator from
0-5VDC operation to 0-10VDC operation. An iso-
lation transformer is also required for this installa-
tion to prevent voltage feedback to the control sys-
tem. The OE266-01 Actuator Interface Module kit

is available from WattMaster. This kit includes both
the MS000204 Interface Module and a 24VAC Iso-
lation Transformer.

Warning: Both the interface module and a 24VAC
isolation transformer must be installed as shown
below when connecting to the Honeywell M7415
or M7405 actuator. Failure to install these com-
ponents as shown can result in serious damage to
the Auto-Zone controller board.