Pid operation – Auto-Zone Control Systems Auto-Zone CV-C Controller Installation Guide (Version 01A) User Manual

Page 38

Advertising
background image

Section 2

Auto-Zone CV-C

2-28

Sequence of Operation

PID Operation

PID Operation

PID Operation

PID Operation

The Hot & Chilled Water Valves are controlled via a Proportional, Integral, Derivative (
PID ) loop. This method of control provides accurate temperature control with minimal
adjustments to the valve position. The best method of explaining the PID operation is to
show a simplified form of the formulas incorporated into the controller code.

The following abbreviations will be used in the formula:

TimeSP

= Integrating Interval

HotSP

= Supply Air Temperature Setpoint

Kp

= Proportional Constant

Ki

= Integral Constant

Kd

= Derivative Constant

P

= Proportional Error

I

= Integral Error

D

= Derivative Error

HWValve

= Calculated Valve Position

SupplyAir

= Current Supply Air Temperature Reading

IF the TIMER has exceeded the TimeSP THEN

Error = HotSP - SupplyAir
P

= ( Error x ( Kp / 100 )) x 100

I

= ( Error x ( Ki / 10))

D

= ( Error - OldError ) x ( Kd / 10 )

HWValve =

P + I + D

OldError

= Error

“ Save current error for next time “

END ROUTINE

The Error is the difference between the Setpoint and the actual Temperature. The P error
uses a limited amount of this error to create a proportional only valve position. For
example, if the Kp was set to 10 then a 10°C temperature error would cause the P error
to set the valve 100% open.

10° Error = ( 10 x ( 10 / 100)) x 100 = 100%
5° Error
= ( 5 x ( 10 / 100)) x 100 = 50%

Advertising