Cv-c humidity sensor wiring, Cvchumid1.cdr auto-zone, Cv- c controller – Auto-Zone Control Systems Auto-Zone CV-C Controller Installation Guide (Version 01A) User Manual

Page 5

Advertising
background image

Notes:

C

O

N

T

R

O

L

S

FILENAME

DATE:

B. CREWS

DESCRIPTION:

PAGE

DRAWN BY:

CV-C Humidity Sensor Wiring

JOB NAME

1.)24 VAC Must Be Connected So

That All Ground Wires Remain

Common.

2.)All Wiring To Be In Accordance

With Local And National Electrical

Codes And Specifications.

06/01/00

CVCHUMID1.CDR

Auto-Zone

1

CV- C Controller

CV- C Controller

EXPANSION

EXPANSION

SENSOR

SENSOR

PRESSURE

PRESSURE

GND

GND

7

7

AIN

AIN

AOUT2

AOUT2

AOUT1

AOUT1

AIN

AIN

GND

GND

GND

GND

5

5

AIN

AIN

AIN

AIN

AIN

AIN

4

4

3

3

2

2

T'STAT

T'STAT

NETWORK

NETWORK

16

16

TOKEN

TOKEN

32

32

8

8

4

4

AIN

1

AIN

1

12V

12V

PU1

PU1

PU2

PU2

PU3

PU3

PU4

PU4

PU5

PU5

PU7

PU7

INPUTS

INPUTS

1

1

2

2

250 ohm Resistor

Installed Between the

AIN2 Input Terminal

and the GND Terminal

Resistor Must be of 1%

Accuracy or Better

+

+

-

-

4-20ma

Sensor

0 - 5 VDC

Sensor

The Pull-up Resistor (PU2),

for the Associated In

Must be Removed When a

4-20ma Sensor is Used

put (AIN2),

The Pull-up Resistor (PU4),

for the Associated In

Must be Removed When a

0-5 VDC Sensor is Used

put (AIN4),

Note: Terminal that is Labeled

“12V” on the Terminal Block

has been Electrically Modified

and is Actually 24 Volts

Note: Terminal that is Labeled

“12V” on the Terminal Block

has been Electrically Modified

and is Actually 24 Volts

4-20ma Sensor Installation

0-5VDC Sensor Installation

Advertising