Cv-c controller wiring, Cvcwir1.cdr oe747, Address add address add – Auto-Zone Control Systems Auto-Zone CV-C Controller Installation Guide (Version 01A) User Manual

Page 4: Cv- c controller

Advertising
background image

Notes:

C

O

N

T

R

O

L

S

FILENAME

DATE:

B. CREWS

DESCRIPTION:

PAGE

DRAWN BY:

CV-C Controller Wiring

Line Voltage

See Note 1

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Comm Loop Wiring Is

Straight Thru

Required VA For Transformer

Each CV-C Controller = 20VA Max.

24VAC

GND

16

8

4

2

1

Caution!

CV-C Controllers Must Have Address Switches Set Between 1

And 30 When Used With CV or CV-EX Systems. Auto-Zone

Plus Systems Require That The Address Switches Be Set

Between 18 And 30.

Local Loop RS-485

9600 Baud

(See Note 3).

Connect To Next Controller And/Or

MiniLink On Local Loop

Address Switch Shown Is

Set For Address 1

Address Switch Shown Is

Set For Address 13

Controller

Address Switch

This Switch Must Be

In The ON Position

As Shown

These Switches Should Be

In The OFF Position

As Shown

Note:

The Power To The CV-C Controller Must Be Removed And

Reconnected After Changing The Address Switch Settings In Order

For Any Changes To Take Effect.

Caution:

Disconnect All Communication Loop Wiring From The CV-C Controller

Before Removing Power From The CV-C Controller. Reconnect Power

And Then Reconnect Communication Loop Wiring.

ADDRESS

ADD

ADDRESS

ADD

ADDRESS

ADD

The Address For Each Controller

Must Be Unique To The Other Controllers

On The Local Loop

JOB NAME

1.)24 VAC Must Be Connected So

That All Ground Wires Remain

Common.

2.)All Wiring To Be In Accordance

With Local And National Electrical

Codes And Specifications.

3.)AllCommunication Wiring To Be

2 Conductor Twisted Pair With

Shield. Use Belden #82760 Or

Equivalent.

07/08/99

CVCWIR1.CDR

OE747

1

Note:

Set-up, Programming And Monitoring Of The CV-C Controller Requires The

Use Of A Personal Computer And ZoneView AZ Software.

EXPANSION

SENSOR

PRESSURE

GND

7

AIN

AOUT2

AOUT1

AIN

GND

GND

5

AIN

AIN

AIN

4

3

2

T'STAT

24VAC

NETWORK

16

TOKEN

32

8

4

GND

AIN

1

12V

INPUTS

R

SHLD

T

COMM

1
2

YS101718

TUC5R PLUS

C

O

M

1-3

R5

C

O

M

4-5

R4

R3

R2

R1

R - Fan ON/OFF Only

GND

AUX

TMP

NORMAL

OVR

R

E

L

O

C

R

E

M

R

O

A

W

Room Sensor

Connection To

AUX Terminal is Reqd

Only When Sensor

Is Specified With

Slide Adjust Option

AIN2 Thru AIN5 & AIN7 May Be User

Configured For The Following:

0 - Not Used ( Nothing connected to this input)

1 - Slide Offset

(Requires Flush Mount Wall Sensor)

2 - Supply Air Temperature

3 - Return Air Temperature

4 - Mixed Air Temperature

5 - Outdoor Air Temperature

(Will broadcast to ALL other controllers)

6 - Humidity Sensor (4-20 mA scaling)

7 - Humidity Sensor (0-5 VDC scaling)

8 - CO² Sensor (4-20 mA scaling)

9 - CO² Sensor (0-5 VDC scaling)

10- Relief Pressure Sensor

(Requires 0-5 VDC ±0.3" WG Sensor)

11 - Dirty Filter Contact (Normally Open)

12 - Alarm Contact (Normally Open)

13- Alarm Contact (Normally Closed)

14- Fan Status Contact (Normally Open)

AIN6 (Phone Jack) Can Only Be Configured

For An Airflow Sensor And Is Used For

Status or To Verify Fan Operation Only

Relay Outputs R2 Thru R5 May Be User

Configured For The Following:

0 - Not Used (Nothing connected to this

output )

1 - Heating Stage

2 - Cooling Stage

3 - Humidifier Enable

4 - De-Humidifier Enable

5 - Scheduled Relay from Internal Schedule

6 - Scheduled Relay from External Schedule

(Only 1 Available!)

AOUT1 & AOUT2 May Be User Configured For

The Following:

0 - Not Used (Nothing connected to this output)

1 - Economizer

(Requires Supply or Mixed Air Sensor

2 - Relief Fan VFD Signal

(Requires Relief Pressure Sensor)

3 - Chilled Water Valve

(Requires Supply Sensor)

4 - Hot Water Valve (Requires Supply Sensor)

5 - Humidification / De-Humidification

(Requires Humidity Sensor)

Note: All Temperature Sensors Must Be Thermistor Type III

Which Provide 10K Ohms Resistance @77 Deg. F

CV- C Controller