Vent requirements, Installation, Altitude considerations – Avalon Firestyles Vashon-1998 to 1999 User Manual

Page 8

Advertising
background image

8

Installation

(for qualified installers only)

Travis Industries

9 3 5 0 8 1 0 2

0 9 1 0 0 2

Vent Requirements

!

Always maintain the required 1Ó (25 mm) clearance (air space) to combustible materials to prevent a fire
hazard. Do not fill air spaces with insulation.

!

The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas
appliance must use itÕs own separate vent system.

Altitude Considerations

This heater has been tested at altitudes
ranging from sea level to 8,000 feet
(2,400 M). In this testing we have found
that the heater, with its standard orifice,
burns correctly with just an air shutter
adjustment.

!

Failure to adjust the air shutter properly
may lead to improper combustion which
can create a safety hazard. Consult your
dealer or installer if you suspect an
improperly adjusted air shutter.

¥

When the vent passes through a wall,
a wall thimble is required. When the
vent passes through a ceiling, a
support box or firestop is required.
When the vent passes through the
roof, a roof flashing and storm collar
are required. Follow the instructions
provided with the vent (from
Duravent¨) for installing these items.

Use a firestop spacer whenever
passing through a ceiling
(Duravent Part #963)

Vertical Termination
(Duravent Part # 991)

Use a roof flashing and storm collar
whenever passing through the roof
(Duravent Part #953 & #943 or #943S)

8-5/8"

(220 mm)

Use a support box
on exposed vent

Vertical Vent

Requirements

Use a wall thimble
whenever passing
through a wall
(Duravent Part #942)

Horizontal Termination
(Duravent Part #984)

Maintain a minimum 1" (25 mm)
clearance from vent to any combustible
(vent is 6 5/8" (170 mm) diameter)

Minimum
Framing for
wall thimble

Horizontal Vent

Requirements

Minimum framing
for fire stop

8-5/8"

(220 mm)

Maintain a minimum 1"
(25 mm) clearance from
vent to any combustible
(vent is 6 5/8" (170 mm)
diameter)

¥

Use Model GS Direct Vent manufactured by Simpson Dura-Vent

only

(or the Chimney Conversion Kit

- see Addendum #2). Follow the installation instructions included with the vent. For the nearest
Simpson Dura-Vent supplier, call (800) 835-4429. Part numbers and descriptions are listed below.

Straight Lengths

908B

6Ó Pipe Length, Black (interior)

907B

9Ó Pipe Length, Black (interior)

906

12Ó Pipe Length, Galvanized

906B

12Ó Pipe Length, Black (interior)

904

24Ó Pipe Length, Galvanized

904B

24Ó Pipe Length, Black (interior)

903

36Ó Pipe Length, Galvanized

903B

36Ó Pipe Length, Black (interior)

902

48Ó Pipe Length, Galvanized

902B

48Ó Pipe Length, Black (interior)

911B

11Ó to 14 5/8Ó Pipe, Adjustable, Black (interior)

Vent Terminations

981

Snorkel Termination (36Ó rise)

(for basement installations)
982

Snorkel Termination (14Ó rise)

(for basement installations)
984

Horizontal Square Termination

950

Vinyl Siding Standoff

991

Vertical Termination

Elbows

990

90¥ Elbow

990B

90¥ Elbow, Black (interior)

945

45¡ Elbow

945B

45¡ Elbow, Black (interior)

Penetration, Support Parts

942

Wall Thimble

940

Optional Wall Thimble Cover

941

Cathedral Ceiling Support Box

943

Flashing, 0/12 to 6/12 Roof Pitch

943S

Flashing, 7/12 to 12/12 Roof

Pitch
953

Storm Collar

963

Ceiling Firestop

988

Wall Strap

¥

Apply high-temperature silicone to the inner and outer pipe before
assembling the sections (on the male, upper section). This seals the
inner pipe from the outer pipe. Slide the sections together and turn 1/4
turn until the sections lock in place. Install three metal screws through
each joint to lock the outer section in place (see the instructions included
with the vent for further details).

NOTE: You may screw the first section of vent to the appliance.

¥

Horizontal sections require a 1/4Ó rise every 12Ó of travel

Apply a 1/8" (3 mm)
bead of high-
temperature silicone
to the inner and
outer pipe. The
silicone must seal
the inner pipe from
the outer pipe.

Silicone

Silicone

+

Exterior Vent Diameter = 6-5/8Ó , Inner Vent Diameter = 4Ó

¥

Horizontal sections require non-combustible support every 36Ó (e.g.: use plumbing tape)