350

9424200994 Rev N

BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Transformer Setup

HMI Navigation Path: Settings Explorer, System Parameters, Transformer Setup

Figure 270. Transformer Setup Screen

Table 114. Transformer Settings

Setting

Range

Increment

Unit

Default

Tap Calculation Mode

Manual or Automatic

n/a

n/a

Manual

MVA Rating

0.5 to 10,000

0.1

n/a

0.5

kV Rating

0.01 to 1,000

n/a

n/a

n/a

Tap

2 to 20 (5A CTs) or 0.4 to 4 (1A CTs)

0.01

n/a

2.00

CT Connection

Set on the Sensing Transformers screen

n/a

n/a

n/a

Phase CT Ratio

Set on the Sensing Transformers screen

n/a

n/a

n/a

Transformer Connection

WYE, DAB, DAC, ZAB, ZAC, NA

n/a

n/a

WYE

Ground Connection

Yes or No

n/a

n/a

No

Differential Circuit

Primary, Secondary, or None

n/a

n/a

Primary

Polarity

Yes or No

n/a

n/a

No

Phase Relationship

A, B, or C

n/a

n/a

A

Connection Settings for Current Differential

When the zone of protection includes a transformer, it may be necessary to provide phase angle and zero
sequence compensation to the currents used by the Phase Current Differential Protection (87) element.
See Figure 271 and Figure 272. For each input circuit, a setting is provided to enter the transformer
connections associated with that input.

Configuration

BE1-11g