87n - neutral current differential protection – Basler Electric BE1-11g User Manual

Page 573

Advertising
background image

9424200994 Rev N

561

* Recognition time = 2 cycles for 0.57 > pickup, 4 cycles for 0.24 > pickup, 8 cycles for 0.08 > pickup, 16
cycles at pickup

O/U/ROC Voltage Inhibit
Setting Range ........................................................... 15 to 250 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

87 - Phase Current Differential Protection (Optional)

Restrained Differential
5 Ampere CT Pickup Accuracy .................................

±4% or ±75 mA, whichever is greater

1 Ampere CT Pickup Accuracy .................................

±4% or ±25 mA, whichever is greater

Response Time ......................................................... <2 cycles at 5 times pickup

<3 cycles at 1.5 times pickup

TAP
5 Ampere CT Setting Range ..................................... 2.00 to 20.0 A
1 Ampere CT Setting Range ..................................... 0.40 to 4.00 A

Minimum Restraint Pickup (I

op

)

Setting Range ........................................................... 0.1 to 1.00 per unit

2

nd

Slope Pickup (I

res

)

Setting Range ........................................................... 0.1 to 20.0 per unit

Restraint Slope 1
Setting Range ........................................................... 5 to 100%

Restraint Slope 2
Setting Range ........................................................... 15 to 140%

Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy....................................................................

±0.5% or ±½ cycle, whichever is greater, plus trip

time for instantaneous response (0.0 setting)

*

* Trip Time for 0.0 Delay Setting .............................. 1¼ cycles maximum for currents ≥ 5 times the pickup

setting. 1¾ cycles maximum for a current of 2
times pickup. Two cycles maximum for a current
of 1.05 times the pickup setting.

87N - Neutral Current Differential Protection

Iop Minimum Pickup

5 Ampere CT

Setting Range ........................................................... 0.1 to 5 A
Accuracy....................................................................

±3% or ±75 mA, whichever is greater

1 Ampere CT

Setting Range ........................................................... 0.02 to 1 A
Accuracy.................................................................... 5 A CT:

±3% or ±15 mA, whichever

Overcorrection Coefficient
Setting Range ........................................................... 1 to 1.3

BE1-11g

Specifications