27x - auxiliary undervoltage protection, 32 - power protection – Basler Electric BE1-11g User Manual

Page 567

Advertising
background image

9424200994 Rev N

555

27X - Auxiliary Undervoltage Protection

Pickup
Setting Range ........................................................... 1 to 150 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Reset/Pickup Ratio .................................................... 102%

±1%

Inhibit Level
Setting Range ........................................................... 1 to 150 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Reset/Inhibit Ratio ..................................................... 102%

±1%

Timing Mode

Definite Timing

Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±0.5% or ±2 cycles, whichever is greater

Inverse Timing

Setting Range ........................................................... 0 to 9.9
Accuracy....................................................................

±5% or ±2 cycles, whichever is greater
Refer to the

Time Curve Characteristics

chapter for

information on available timing curves.

32 - Power Protection

Pickup
5 Ampere CT Setting Range ..................................... 1 to 6,000 W, three-phase
1 Ampere CT Setting Range ..................................... 1 to 1,200 W, three-phase
Accuracy....................................................................

±3% of setting or ±2 watts, whichever is greater,

at unity power factor. (Accuracy of phase
relationship measurement between V and I is
accurate to within 0.5 degrees when I is greater
than 0.1 Aac and V is greater than 5 Vac. The
power and var measurements at power factor
other than 1.0 are affected accordingly.)

Dropout ...................................................................... 95 to 99% of the actual pickup value

Time Delay
Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±0.5% or ±2 cycles, whichever is greater

40Q - Loss of Excitation Protection - Reverse var Based

Pickup
5 Ampere CT Setting Range ..................................... 1 to 6,000 var
1 Ampere CT Setting Range ..................................... 1 to 1,200 var
Accuracy....................................................................

±3% or ±2 var, whichever is greater

Dropout ...................................................................... 93 to 99% of the actual pickup value

Time Delay
Setting Range ........................................................... 1 to 600,000 ms
Accuracy....................................................................

±0.5 or ±2 cycles, whichever is greater

40Z - Loss of Excitation Protection - Impedance Based

Offset impedance mapping can be used to protect against a loss of field (under impedance). Two circular
tripping zones are used on the impedance plane (R and X). Figure 332 illustrates 40Z offset impedance
mapping.

BE1-11g

Specifications