Functional test report, Delay timer verification, Control timer verification – Basler Electric BE1-11g User Manual

Page 462

Advertising
background image

450

9424200994 Rev N

Table 195. Control Time Delay Settings

Setting

Value

BESTCOMSPlus Screen

Description

Phase Pickup

1 A

Protection, Current, Breaker Fail (50BF)

Sets phase pickup to 1 A

Ground Pickup

1 A

Protection, Current, Breaker Fail (50BF)

Sets ground pickup to 1 A

Control Timer

100 ms

Protection, Current, Breaker Fail (50BF)

Sets control timer to 100 ms

Delay Timer

200 ms

Protection, Current, Breaker Fail (50BF)

Sets delay timer to 200 ms

Pickup

2 A

Protection, Current, Instantaneous
Overcurrent (50-1)

Sets pickup to 2 A

Step 13: (Optional.) Repeat steps 1 through 12 for the B and C phase elements. Note: Set 50-1 mode to

IB for B-phase and IC for C-phase.

Step 14: (Optional.) Repeat steps 7 through 13 with CT Circuit 2 as the source for protection systems

equipped with two sets of CTs. In step 12, replace D1 with F1, D2 with F2, etc.

Functional Test Report

Delay Timer Verification

Delay Timer Range = 50 to 999 ms

Delay Timer Accuracy =

±0.5% or +1¼, −0.5 cycles, whichever is greater

Step

Delay Timer Setting

Low

Actual Timing

High

Pass/Fail

4

100 ms

92 ms

120 ms

P / F

6

200 ms

192 ms

220 ms

P / F

6

300 ms

292 ms

320 ms

P / F

Control Timer Verification

Control Timer Range = 50 to 99 ms

Control Timer Accuracy =

±0.5% or ½ cycle, whichever is greater

Step

Control Timer Setting

Low

Actual Timing

High

Pass/Fail

12

100 ms

92 ms

120 ms

P / F

Breaker Fail (50BF) Test

BE1-11g

Advertising