Instantaneous overcurrent (50) element, Be1-50/51b-218 pickup, Be1-50/51b-228 pickup – Basler Electric BE1-50/51B-218 User Manual

Page 15: Dropout, Curve characteristics, Instantaneous overcurrent (50) element -5

Advertising
background image

1.0

10.0

100.0

0.000

0.200

0.400

0.600

0.800

1.000

1.200

Multiple of Pickup

x

R

D (Second

s

)

P

0

04

6-

1

1

Vertical axis xRD (Seconds) is applicable for all curves and is derived from
multiplying the constant R for the curve selected times D (the Time Dial setting).

Figure 1-1. Integrating Reset Characteristic Curve

Instantaneous Overcurrent (50) Element

Setting the INST PICKUP control to the minimum pickup setting places the relay in the most sensitive
state and may be used as a safety setting.

BE1-50/51B-218 Pickup

Setting Range:

1 to 99 Aac

Setting Increment:

1 Aac

Accuracy:

±2%, ±25 milliamperes at or above 1.0 ampere setting

BE1-50/51B-228 Pickup

Setting Range:

0.2 to 19.8 Aac

Setting Increment:

0.2 Aac

Accuracy:

±2%,

±5

milliamperes at or above 0.2 ampere setting

Dropout

Dropout occurs at 95% of pickup value.

Curve Characteristics

Instantaneous characteristic curves are similar to standard electromechanical instantaneous units.
However, the time to trip for applications where the initial current through the relay is less than 0.4
ampere (5 ampere relay) or 0.08 ampere (1 ampere relay) may be slightly longer. This may occur on a
very lightly loaded circuit or when the relay is providing ground protection and is connected to measure
neutral current. Figure 1-2 shows the instantaneous characteristic curves for maximum time to trip.

An additional fixed delay of 0.1 second may be added with internal switch SW3-2. This delay applies to
both phase and ground applications. Closing switch SW3-2 provides an additional delay of 0.1 second.
Section 2 illustrates the location of SW3.

The instantaneous element in BE1-50/51B-218 and BE1-50/51B-228 relays may be set lower than the
instantaneous element in IAC relays and still have the same reach. This is because the BE1-50/51B-218
and BE1-50/51B-228 instantaneous element effectively eliminates the fault current transient overreach
components. When calculating BE1-50/51B-218 and BE1-50/51B-228 relay instantaneous element
settings, calculate the symmetrical value without any adder for transient overreach.

9252000995 Rev H

BE1-50/51B-218/-228 General Information

1-5