9252000995 Rev H

BE1-50/51B-218/-228 Controls and Indicators

2-3

Table 2-1. BE1-50/51B-218 and BE1-50/51B-228 Controls and Indicators (Refer to Figures 2-1 and 2-2)

Locator

Control or Indicator

Function

A

INST MANUAL TRIP
Test Points

When shorted, the test points (jacks) provide a secure means to
manually trip the controlled breaker. Jacks accept a standard 0.08
inch diameter phone tip plug.

B INST

PICKUP

Selectors

Two switches (TENS and UNITS) to select pickup current in
amperes. Changing switch selectors while the relay is in service
may cause tripping.

C Targets

Red target indicators latch when the trip circuit current is greater
than 0.2 amperes. One target each for TIME and INST.

D TIME

PICKUP

Selectors

Two switches (UNITS and TENTHS) to select pickup current in
amperes. Changing switch selectors while the relay is in service
may cause tripping.

E

CURVE Selector

Ten position selector switch to select one of nine inverse functions
or one fixed time function.

F

TIME DIAL Selectors

Two selector switches (UNITS and TENTHS) to select the desired
characteristic curve. A setting of 0.0 results in instantaneous
operation without any intentional delay. A setting of 9.9
corresponds to the typical time provided by an electromechanical
relay at its maximum dial setting.

G

TIME MANUAL TRIP
Test Points

When shorted, the test points provide a secure means to manually
trip the controlled breaker. Jacks accept a standard 0.08 inch
diameter phone tip plug.

H

ACTIVE/PICKUP LED

Red LED indicates sensed current has exceeded the TIME
PICKUP setting. LED turns from red to green when sensed current
falls below 95% of pickup setting. When the LED is green, the
relay is active but has not picked up.

I

Target RESET Button

Linkage extends through back of front cover to reset both gravity
latched target indicators.

SW3-1

SW3-1 selects the system operating frequency. SW3-1 open
(OFF) selects 60 Hz operation. SW3-1 closed (ON) selects 50 Hz
operation.

SW3-2

SW3-2 provides additional time delay for the instantaneous
element. Closing switch SW3-2 (ON) provides an additional
instantaneous delay of 0.1 second.

SW3-3

SW3-3 provides selection of GE IAC type curves or ABB type
curves. Closing switch SW3-3 (ON) selects GE IAC type curves
(refer to Table 1-3). Opening switch SW3-3 (OFF) selects ABB
type curves (refer to Table 1-2).

SW3

SW3-4

SW3-4 provides selection of either instantaneous or integrating
reset characteristics. Closing SW3-4 (ON) selects integrating reset
characteristics. Opening SW3-4 (OFF) selects instantaneous reset
characteristics.

 NOTE: In Revision G and previous relays, switch SW3 is designated as SW8.