Frequency selector settings – Basler Electric BE1-81O/U User Manual

Page 44

Advertising
background image

38

9137300990 Rev N

Figure 28. BE1-81O/U Test Setup

Frequency Selector Settings

1.

Connect the relay as shown in Figure 28.

2.

Adjust the front panel, Setpoint 1 controls to the following settings:

Over/Under Selector Switch: Under (U) position

Frequency Selector Switch: 51.11

3.

Apply operating power to the relay.

4.

Apply 60-hertz voltage to the relay sensing input. The level of voltage must exceed the setting of the
adjustable, front-panel Undervoltage Inhibit control.

Testing

BE1-81O/U