Frequency setpoint, Time delay, Undervoltage inhibit – Basler Electric BE1-81O/U User Manual

Page 48: Type tests

Advertising
background image

42

9137300990 Rev N

Current-operated targets require a minimum trip-circuit current of 200 milliamperes and have a continuous
rating of 3 amperes, a two-minute rating of 7 amperes, and a one-second rating of 30 amperes.

Internally-operated targets should be selected if the relay has normally-closed output contacts.

Frequency Setpoint

Range ................................................................... 40 to 70 Hz
Increment ............................................................. 0.01 Hz
Accuracy...............................................................

±0.01 Hz of the setpoint setting

Time Delay

Setting Range
Cycles (of applied frequency)............................... 3 to 99 cycles in 1 cycle increments

10 to 990 cycles in 10 cycle increments

100 to 9,900 cycles in 100 cycle increments

Seconds ............................................................... 0.1 to 9.9 seconds in 0.1 second increments

1.0 to 99 seconds in 1 second increments

10 to 990 seconds in 10 second increments

Accuracy
Cycles ................................................................... +2 cycles or

–1 cycle for 0.02 Hz to 1 Hz frequency

variation from setpoint setting

±1 cycle for frequency variation greater than 1 Hz from

setpoint setting

Seconds ...............................................................

±2% of the setting or ±50 ms, whichever is greater for

0.02 Hz to 1 Hz frequency variation from setpoint
setting

±2% of the setting or ±25 ms, whichever is greater for

frequency variation greater than 1 Hz from
setpoint setting

Undervoltage Inhibit

Setting Range ...................................................... 40 to 120 Vac
Accuracy...............................................................

±5% of the setting at 25°C for nominal frequency input

Type Tests

Dielectric Strength

Meets IEC 60255-5 and exceeds IEEE C37.90 one-minute dielectric tests as follows:
All circuits to ground ............................................. 2,828 Vdc
Input to output circuits .......................................... 2,000 Vac or 2,828 Vdc

Surge Withstand Capability

Qualified to IEEE C37.90.1-1989

Fast Transient

Qualified to IEEE C37.90.1-1989

Impulse

Qualified to IEC 60255-5

Radio Frequency Interference

Maintains proper operation when tested in accordance with IEEE C37.90-1989.

Specifications

BE1-81O/U