Figure 4-11. configure ethernet port -9 – Basler Electric DGC-2020 User Manual

Page 119

Advertising
background image

3. Click the Edit button to change settings. After settings are configured, click the Edit button again to

exit.

4. Use the Left arrow key to navigate back to the LSM Setup screen on the front panel HMI. After

leaving the leaving the TCP/IP Settings screen, the LSM-2020 will reboot and use the new settings.

Alternate Method to Configure LSM-2020 Network Settings through the DGC-2020

1. Navigate to the Settings, System Params, Remote Module Setup, LSM Setup screen on the front

panel HMI and verify that the LSM-2020 is enabled with the correct CANBus address so that the
DGC-2020 and LSM-2020 are properly linked together. If a USB connection to the DGC-2020 is
active, the LSM-2020 enable setting and CANBus address can be found by using the Settings
Explorer in BESTCOMSPlus to open the System Parameters, Remote Module Setup tree branch.
The DGC-2020 will annunciate a pre-alarm if the LSM-2020 is not connected properly when it is
enabled. If the connection is valid, the network settings of the LSM-2020 can be configured through
the USB interface of the DGC-2020.

2. Connect to the DGC-2020 through the USB port as described under USB Communication. Select

Configure, Ethernet from the File pull-down menu. If the LSM-2020 is connected properly, the
Configure Ethernet Port screen shown in Figure 4-11 will appear.

Figure 4-11. Configure Ethernet Port

Configurable options include:

IP Address:

Internet Protocol Address to be used by the LSM-2020.

Default Gateway:

Default host to send data destined for a host not on the network subnet.

Subnet Mask:

Mask used to determine the range of the current network subnet.

Use DHCP:

Automatically configures IP Address, Default Gateway, and Subnet Mask
via DHCP. This can be used only if the Ethernet network has a properly
configured DHCP server running. The LSM-2020 does not act as a
DHCP server.

The values for these options should be obtained from the site administrator if the LSM-2020 is
intended to share the network with other devices. If the LSM-2020 is operating on an isolated
network, the IP address might be chosen from one of the following ranges as listed in IETF
publication RFC 1918, Address Allocation for Private Networks.

10.0.0.0 - 10.255.255.255

172.16.0.0 - 172.31.255.255

192.168.0.0 - 192.168.255.255